Wärtsilä JOVYTEC PMS 2002K / 3002K   BAX 4837E  

 - 22 -

 

 

7.5  

Manual testing 

 

The UPS unit is capable of performing a self-test. Pressing the key 

FUNC 

causes the unit to run with its 

configurations menu. Navigate to: 

Manual Battery Test. 

Now press the button 

ENTER

. The message 

TEST? 

appears in the display.  If you wish to perform a battery test then confirm by pressing the  

key 

ENTER

. The battery test will now be performed by the UPS unit by itself. The UPS unit will then again run 

by itself in its normal operating mode after the battery test has been performed successfully. 

It is not 

necessary to operate any switches to do this!! 

If the battery is faulty, the message 

E07 

will be shown in the display and a permanent tone will sound. 

Please replace the battery in this case. 

 

 

7.6  

OFFLINE mode 

 

The UPS unit can be operated using special settings via the display or with the software supplied in  

offline mode. This operating mode has the advantage of only using a small amount of energy. 

 

The procedure for setting to OFFLINE mode is as follows: 

 

-  The key 

FUNC

 must be pressed for 2 seconds to obtain configuration mode. 

   The first configuration parameter appears in the display. 

 

-  The key 

FUNC

 can be used to navigate through the parameters. 

 

-  Select the parameter point to be altered using the key 

ENTER

, in this case: HE mode 

 

-  The key 

FUNC

 is then used to navigate through the menu-entries for the selected parameter (ON/OFF). 

 

-  You have the option to select between 10% and 15%, which are the thresholds to be monitored, and if the 

voltage does not meet this criterion then the UPS switches to battery operation. 

 

-  The selected option is confirmed using the key 

ENTER

 and saved by pressing the key again. 

-  Ensure that the settings were adopted in that the display shows: High Efficiency. 

-  The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode  

   after a long period of power loss where the end of the autonomy period was reached and the UPS shut down  

   once the final discharge voltage was reached. 

 

 

7.7  

Free running mode 

 

Short explanation of free running mode: The preset input frequency window of the UPS has a 

range of 45Hz - 65Hz and is referred to in the following as the input frequency range. 

The narrow input frequency range has a frequency range of 49Hz - 51Hz. This range can be set via the display 

and operates in the following ranges: 

 

I/P input frequency low = 50 x (1-0.02) = 49Hz                           I/P input frequency high = 50 x (1+0.02) = 51Hz 

 

 

7.7.1 

Free running ON 

 

If  the  input  frequency  is  49.3Hz,  this  value  is  within  the  narrow  input  frequency  range.  This  means  that  the 

output frequency is also 49.3Hz (synchronised) and the UPS unit runs in line mode. If the input frequency then 

drops below 49Hz, for example 48Hz, the input frequency is outside the narrow input frequency range but still 

within the broader input frequency window. The output frequency will therefore be 50Hz and the UPS unit will 

remain in line mode. If the input frequency were 43Hz then it would be outside both the narrow and the broader 

input frequency window. The UPS unit switches to battery operation and supplies the load via the inverter with 

50Hz. 

 

 

7.7.2 

Free running OFF 

 

If  the  input  frequency  is  49.3Hz,  this  value  is  within  the  narrow  input  frequency  range.  This  means  that  the 

output frequency is also 49.3Hz (synchronised) and the UPS unit remains in line mode. If the input frequency 

then  drops  below  49Hz,  for  example  48Hz,  then  the  input  frequency  is  outside  the  specified  values  for  the 

narrow  input  frequency  range  and  the  UPS  unit  switches  to  battery  operation  and  supplies  the  load  via  the 

inverter with 50Hz. 

Summary of Contents for BAX 4837

Page 1: ...l un I Jet _________ __ Jovyatlas Jovytec PMS 2002K 3002K https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva jovytec pms 2002k 3002k html...

Page 2: ...BAX 4837 Operating manual W rtsil JOVYTEC PMS 2002K 3002K...

Page 3: ...JOVYTEC PMS 2002K 3002K BAX 4837E 2 Index Date Name Issue 0 2013 04 03 A Heller Original 1 2014 11 07 Chr Fechteler 14 608 2 2015 11 12 Chr Fechteler 15 609 3 2015 12 04 Chr Fechteler 15 651 4 5 6 7...

Page 4: ...are not part of the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in t...

Page 5: ...W 15 5 3 INSTALLATION 16 6 ELECTRICAL CONNECTION 17 6 2 COMMISSIONING THE UPS UNIT 18 6 3 SHUTTING DOWN THE UPS UNIT 18 7 OPERATING AND INDICATING ELEMENTS 19 7 1 LED AND FUNCTION KEYS 19 7 2 PARAMETE...

Page 6: ...SIGNMENT OF THE RS232 INTERFACE 25 9 3 USB PORT OPTIONAL 26 10 SPECIAL EQUIPMENT 26 10 1 ELECTRONIC STOP FUNCTION 26 11 MANUAL BYPASS OPTIONAL 26 12 POTENTIAL FREE SIGNALS FROM THE RELAY CARD OPTIONAL...

Page 7: ...l discharging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the lo...

Page 8: ...on During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating volt...

Page 9: ...eans that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in...

Page 10: ...to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Load transfer characteristic Power failure 0 ms Overload switching Automatic tra...

Page 11: ...ar load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 95 according to the operating mode Load transfer characteristic Power failure 0 ms O...

Page 12: ...inear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10 seconds Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Load transfer characteristic Power failure 0 m...

Page 13: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 12 2He 19 428 425 5 Dimensions and views Picture 1 Front view Picture 2 Top view...

Page 14: ...LED operation lights green if the UPS is switched on 9 LED operation lights green when in UPS and bypass mode and signalises that the output voltage is present 10 LED battery operation lights yellow...

Page 15: ...interface Relay board or SNMP 2 RS 232 Interface 3 Cover for optional USB Interface 4 Fan 5 Battery jack external battery pack l 6 UPS output 7 UPS Input C13 plug 8 Input fuse 15A 2002K Input fuse au...

Page 16: ...C PMS 2002K 3002K BAX 4837E 15 5 2 Powerpack Front and Rear View Picture 10 Front view 1 2 Picture 11 Rear view Position Designation 1 Connecting jack for an optional additional battery pack 2 Battery...

Page 17: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 16 5 3 Installation For installation the two supplied angles are to be mounted on both sides as shown on the sketch...

Page 18: ...connecting up work is now complete P L E A S E N O T E Only trained personnel are allowed to work on the UPS unit Observe all corresponding safety regulations Marking of cables is to be according to...

Page 19: ...while pressing the ON OFF button and the message Switching off soon appears in the display and then the message UPS OFF The UPS unit is now shut down Please note The internal fans of the UPS will con...

Page 20: ...ch as the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER button selects the p...

Page 21: ...f the UPS BAT VOLT 81V Battery voltage of the battery pack O P LOAD 80 Utilisation of the UPS as a percentage O P W 1400W Output in Watts O P VA 2000VA Output in VA O P CURR 13A Output current in A BA...

Page 22: ...UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for a permanent manual bypass Man bypass...

Page 23: ...ere adopted in that the display shows High Efficiency The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode after a long period of power loss w...

Page 24: ...Result The UPS unit will not switch to bypass not activated since the preset parameter has not been maintained and the bypass is deactivated 7 8 2 Free running ON bypass activated Example Input volta...

Page 25: ...ary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the servi...

Page 26: ...UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer T...

Page 27: ...the UPS unit If the electronic STOP functionality is to be used then the bridge should be removed on the plug and an external switch opener clamped to the rear plug Actuation of the external electroni...

Page 28: ...to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restarted There...

Page 29: ...W rtsil JOVYTEC PMS 2002K 3002K BAX 4837E 28...

Page 30: ...er continues to run automatically until the battery is charged up Restoration of mains power after total discharge of the battery At the end of the backup time the inverter switches off automatically...

Page 31: ...life of batteries 10 12 years 6 9 years 3 5 years Temperature Expected working life of batteries 20 C 12 years 9 years 5 years 30 C 5 years 4 years 2 5 years 40 C 2 5 years 2 years 1 25 years 13 4 Ins...

Page 32: ...Proceed as follows to replace the battery Note Exchanging the battery could lead to a power outage on the output when the input power fails during the procedure 1 Disconnect all battery racks form the...

Page 33: ...___________________________________________________________________________________ ______________________________________________________________________________________ _____________________________...

Reviews: