background image

 

 

JOVYATLAS POWERMASTER S 6000-P       BAX 4469 E                                                     

  -  25 -

 

 

15 

POWERPACK S 6000 

 
 

15.1 

Longer backup times 

 

The UPS unit needs two or more battery racks to achieve longer backup times. 
The POWERMASTER S 6000 allows one to switch up to two battery packs in parallel, which results in the  
following backup times: 

 
 
 
 
 
 

 
 
 

 

 
 
 
 
 
 
 
 
 
 

15.2 

Battery operation 

 
In the case of a network failure the consumers are supplied without interruption from the battery. 

 

In battery operation the LED 

ON - BATT 

lights up and an acoustic warning tone sounds every 5 seconds. 

The  characteristic  of  the  acoustic  warning  tone  changes  towards  the  end  of  the  backup  time,  when  the 
battery is depleted, to a double-beep every 5 seconds. The backup time of a number of minutes generally 
allows targeted switching off of consumers or data storage/back-up when operating a PC, without losing data 
or  having  running  processes  interrupted  in  an  uncontrolled  manner.  The  backup  time  can  be  extended 
significantly by switching off individual, less important consumers. 
 

Restoration of mains power before total discharge of the battery: 

 
In the case of restoration of the mains power before the end of the bridging time, the inverter continues to 
run automatically until the battery is charged up. 
 

Restoration of mains power after total discharge of the battery: 

 
At  the  end  of  the  bridging  time  the  inverter  switches  off  automatically  and  the  consumers  are 

no

  longer  

supplied with power.  
 
When the mains power is restored, the consumers begin again to be supplied  with power via the inverter. 
The  inverter  is  switched  on  again  automatically.  The  battery  is  charged  up  again  automatically  after 
restoration of the mains power. 
 

 

Number of slots 

Number of 

batteries 

Total weight of 

battery pack incl. battery 

Total weight of 

UPS + battery pack 

Autonomy time 
at 100% load 

Autonomy time 
at 80% load 

Autonomy time 
at 50% load 

 

20 

66kg 

86kg 

9min. 

12min. 

21min. 

40 

132kg 

152kg 

25min. 

32min. 

58min. 

60 

198kg 

218kg 

45min. 

58min. 

107min. 

 

P L E A S E   N O T E

 

Before plugging in the battery plug, the voltage at the battery jack on the UPS unit and the battery 
used must be checked to ensure that they both have the same voltage and polarity. The attached 
markings  (DIRECT  CURRENT  LINK  VOLTAGE)  and  a  control  measurement  using  a  suitable  
measuring device serve to achieve this. The battery is not galvanically isolated from the mains so 
occurrence  of  a  mains  voltage  at  the  battery  terminals  is  possible.  The  UPS  unit  should  be 
disconnected from the mains before working on the battery. Do not cover the ventilation slits on the 
battery slots in order to avoid any excessive increase in the battery temperature. The battery rack 
should be connected to the mains and switched  on  at the latest 4  weeks after receipt in order to 
prevent battery self-discharging. 

Summary of Contents for JOVYATLAS POWERMASTER S 6000-P

Page 1: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 1 Operating Manual UPS System POWERMASTER S 6000 P BAX 4469E...

Page 2: ...R S 6000 P BAX 4469 E 2 Index Date Name Remarks 0 2012 04 23 Chr Fechteler Original 1 2014 06 13 Chr Fechteler 14 349 2 2014 11 06 Chr Fechteler 14 608 3 2015 07 22 Chr Fechteler 15 381 4 2015 09 25 C...

Page 3: ...source of information W RTSIL JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating manual without having to make an anno...

Page 4: ...7 2 SHUTTING DOWN THE SINGLE UPS 15 7 3 COMMISSIONING THE UPS IN PARALLEL OPERATION 16 7 4 SHUTTING DOWN THE UPS IN PARALLEL OPERATION 16 8 OPERATION AND DISPLAYPANEL 17 8 1 PANEL 17 8 2 PARAMETER OF...

Page 5: ...4 weeks after receipt in order to prevent the battery discharging itself 1 General Notes The device may only be opened by trained specialists The system is to be connected up and earthed according to...

Page 6: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Page 7: ...pass operation In the case of a fault occurring in the inverter or an overload a switch over device switches the load back to the mains This means that in the case of a power failure the connected con...

Page 8: ...ure 0 ms Overload switching Automatic overload switching by the UPS unit Noise level At an approx distance of 1 metre 55dB A Environment Temperature 0 C to 40 C 15 25 C recommended Air humidity 0 to 9...

Page 9: ...BAX 4469 E 9 5 Views of JOVYATLAS Powermaster S 6000 P 5 1 Front and Rear View Figure 4 Front View Figure 5 Rear View and Terminal Block FAN COVER Panel Mounting Angles FAULT BYPASS ON BAT ON LINE ON...

Page 10: ...RPACK S 6000 1 Figure 6 Front View POWERPACK S 6000 3 2 Figure 7 Rear View POWERPACK S 6000 4 Position Designation 1 Cover Plate left and right removable 2 Mounting and Retaining Bracket for 19 mounti...

Page 11: ...outs 5 Connect the input cable to the terminals with the designation input L N PE 6 Connect the output cable to the terminals with the designation output L N PE 7 Fix the cover plate with a Phillips s...

Page 12: ...cted in between the feeding mains and the UPS Figure 8 Using Reverse Voltage Protection If the reverse voltage protection is not used please connect the inputs like shown in picture below Figure 9 Wit...

Page 13: ...Anlagen wird ein Kabel von USV 1 nach USV 2 sowie ein Kabel von USV 2 nach USV 3 geschaltet Es darf keine Ringverbindung geschaffen werden Figure 10 Connection of external Battery Packs 6 4 Connection...

Page 14: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 14 Figure 11 Connection of a Parallel System UPS UPS UPS UPS Load MAINS...

Page 15: ...ting down the single UPS 1 Push Button MENU ENTER to choose Menu UPS Command 2 Push Button MENU ENTER to choose Menu Start UPS ON OFF 3 Push Button MENU ENTER to choose Menu UPS runs to Bypass 4 Open...

Page 16: ...Please check if all BYPASS LED s are not lighting all ON LINE LED are lighting the display will show message Line Mode Parallel Important Notice Prior to connecting the load to the output of the syste...

Page 17: ...l flash in yellow when input voltage magnitude or frequency is out of tolerance ON LINE This LED will light up in green when the UPS is operating on line mode ON BAT This LED will light up in red when...

Page 18: ...LD START LANGUAGE FAULT REC TIME CLEAR FAULT REC LCD VERSION CORE VERSION UPS SERIAL No DISABLE ENABLE Line config Disable 208 220 230 240V BATT TEST TIME BATT TEST PERIOD AUTO MANUAL TEST 1 2 3 DISAB...

Page 19: ...S O P FREQ 50 0Hz Output Frequency of UPS BAT VOLT 276V Battery Voltage of Battery Pack O P LOAD 80 Load in Percent O P CURR 13A Load Current in Ampere O P W 2300W Load in Watt O P VA 3000VA Load in V...

Page 20: ...al Failure check the PFC Rectifier Inverter fault Internal Failure check the Inverter Over temperature Check Function of the Fan or if something is blocking the Air Outlet Batt over volt Internal Fail...

Page 21: ...llow data transmission between a computer and the UPS unit The UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of powe...

Page 22: ...tion of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again the elec...

Page 23: ...e UPS unit to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be rest...

Page 24: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 24 14 Circuit diagram relay board...

Page 25: ...attery At the end of the bridging time the inverter switches off automatically and the consumers are no longer supplied with power When the mains power is restored the consumers begin again to be supp...

Page 26: ...UPS has to be recharged in case of UPS is being switched off totally after latest four weeks It is sufficient to connect the UPS to an input mains The recharging time shall be at least 8 hours We reco...

Reviews: