JOVYATLAS POWERMASTER S 6000-P       BAX 4469 E                                                     

  - 3 - 

 

N O T E S !

 

 

Notes concerning this operating manual 

 

Thank  you  for  deciding  to  purchase  this  uninterrupted  power  supply  unit  (UPS)  model  JOVYATLAS  POWERMASTER  S  6000  P.  It 
represents reliable protection for the attached consumers. 

 

Please read through this manual very carefully 

 
This manual contains regulations covering safety, installation and operating methods which  will help you  guarantee to obtain the full 
performance und operational readiness which the UPS can offer. 

 

Put this manual in a place of safe keeping  

 
It contains important regulations for safe use of this UPS and for reaching manufacturer services if, for some reason, correct operation 
of the UPS is in doubt. 

 

Keep or reuse the packaging material 

 
The packaging material for the UPS was designed with great care to protect its contents against damage during transport. This material 
is also useful if you ever have to send the UPS back for checking. The warranty provisions do not cover damage that occurs during 
transport. 

 

Duty to instruct persons 

 
This operating manual is to be read through carefully before assembly and first use of the UPS by persons who will be working with or 
on the UPS. 

 

This operating manual is an integral part of the UPS. The operator of this device is required to make this operating manual available in 
an unlimited fashion to every group of persons who transport the UPS, commission it, maintain it or who do any other kind of work on 
this device. 

 

Validity 

 
This operating manual is in line with state-of-the-art UPS technology at its time of publishing. The contents are not part of the  contract 
but simply serve as a source of information. 

 

WÄRTSILÄ  JOVYATLAS  EUROATLAS  GmbH  reserves  the  right  to  make  any  necessary  changes  to  the  contents  and  technology 
described  in  this  operating  manual  without  having  to  make  an  announcement  to  this  effect  WÄRTSILÄ  JOVYATLAS  EUROATLAS 
GmbH  cannot  be  held  responsible  for  any  errors  or  improper  information  in  this  operating  manual  since  there  is  no  duty  upon  the 
company to update this operating manual on an ongoing basis. 

 

Loss of warranty 

 
Our deliveries and services rendered are subject to the General Delivery Conditions for Products of the Electrical Industry as well as  
our  General  Sales  Conditions. We  reserve  full  rights  to  make  any  changes  to  this  operating  manual,  in  particular  to  technical  data, 
operation, dimensions and weights. We request that you make any claims concerning delivered goods within eight days after arrival of 
the goods together with the packing slip. Complaints made later than this cannot be considered. 

 

WÄRTSILÄ JOVYATLAS EUROATLAS GmbH will annul all duties upon WÄRTSILÄ JOVYATLAS EUROATLAS GmbH and its dealers 
such as promises to offer a warranty period, service contracts etc. without warning if any spare parts other than original parts or parts 
are used for maintenance and repair purposes. 

 

Handling 

 
This operating manual for the UPS is constructed in such a way that all work required for commissioning, maintenance and repair can 
be conducted by appropriate skilled personnel. 

 

The Service Hotline 

 

More information is available in Chapter 8 “

Service information

“ about the UPS unit, operating manual, service etc. 

 

Copyright 

 
Any passing on, duplication and/or transfer by means of electronic or mechanical means, also extracts thereof, of this operating manual, 
requires express prior written permission from WÄRTSILÄ JOVYATLAS EUROATLAS GmbH. 

 

Copyright WÄRTSILÄ JOVYATLAS EUROATLAS GmbH. All rights reserved. 

Summary of Contents for JOVYATLAS POWERMASTER S 6000-P

Page 1: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 1 Operating Manual UPS System POWERMASTER S 6000 P BAX 4469E...

Page 2: ...R S 6000 P BAX 4469 E 2 Index Date Name Remarks 0 2012 04 23 Chr Fechteler Original 1 2014 06 13 Chr Fechteler 14 349 2 2014 11 06 Chr Fechteler 14 608 3 2015 07 22 Chr Fechteler 15 381 4 2015 09 25 C...

Page 3: ...source of information W RTSIL JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating manual without having to make an anno...

Page 4: ...7 2 SHUTTING DOWN THE SINGLE UPS 15 7 3 COMMISSIONING THE UPS IN PARALLEL OPERATION 16 7 4 SHUTTING DOWN THE UPS IN PARALLEL OPERATION 16 8 OPERATION AND DISPLAYPANEL 17 8 1 PANEL 17 8 2 PARAMETER OF...

Page 5: ...4 weeks after receipt in order to prevent the battery discharging itself 1 General Notes The device may only be opened by trained specialists The system is to be connected up and earthed according to...

Page 6: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Page 7: ...pass operation In the case of a fault occurring in the inverter or an overload a switch over device switches the load back to the mains This means that in the case of a power failure the connected con...

Page 8: ...ure 0 ms Overload switching Automatic overload switching by the UPS unit Noise level At an approx distance of 1 metre 55dB A Environment Temperature 0 C to 40 C 15 25 C recommended Air humidity 0 to 9...

Page 9: ...BAX 4469 E 9 5 Views of JOVYATLAS Powermaster S 6000 P 5 1 Front and Rear View Figure 4 Front View Figure 5 Rear View and Terminal Block FAN COVER Panel Mounting Angles FAULT BYPASS ON BAT ON LINE ON...

Page 10: ...RPACK S 6000 1 Figure 6 Front View POWERPACK S 6000 3 2 Figure 7 Rear View POWERPACK S 6000 4 Position Designation 1 Cover Plate left and right removable 2 Mounting and Retaining Bracket for 19 mounti...

Page 11: ...outs 5 Connect the input cable to the terminals with the designation input L N PE 6 Connect the output cable to the terminals with the designation output L N PE 7 Fix the cover plate with a Phillips s...

Page 12: ...cted in between the feeding mains and the UPS Figure 8 Using Reverse Voltage Protection If the reverse voltage protection is not used please connect the inputs like shown in picture below Figure 9 Wit...

Page 13: ...Anlagen wird ein Kabel von USV 1 nach USV 2 sowie ein Kabel von USV 2 nach USV 3 geschaltet Es darf keine Ringverbindung geschaffen werden Figure 10 Connection of external Battery Packs 6 4 Connection...

Page 14: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 14 Figure 11 Connection of a Parallel System UPS UPS UPS UPS Load MAINS...

Page 15: ...ting down the single UPS 1 Push Button MENU ENTER to choose Menu UPS Command 2 Push Button MENU ENTER to choose Menu Start UPS ON OFF 3 Push Button MENU ENTER to choose Menu UPS runs to Bypass 4 Open...

Page 16: ...Please check if all BYPASS LED s are not lighting all ON LINE LED are lighting the display will show message Line Mode Parallel Important Notice Prior to connecting the load to the output of the syste...

Page 17: ...l flash in yellow when input voltage magnitude or frequency is out of tolerance ON LINE This LED will light up in green when the UPS is operating on line mode ON BAT This LED will light up in red when...

Page 18: ...LD START LANGUAGE FAULT REC TIME CLEAR FAULT REC LCD VERSION CORE VERSION UPS SERIAL No DISABLE ENABLE Line config Disable 208 220 230 240V BATT TEST TIME BATT TEST PERIOD AUTO MANUAL TEST 1 2 3 DISAB...

Page 19: ...S O P FREQ 50 0Hz Output Frequency of UPS BAT VOLT 276V Battery Voltage of Battery Pack O P LOAD 80 Load in Percent O P CURR 13A Load Current in Ampere O P W 2300W Load in Watt O P VA 3000VA Load in V...

Page 20: ...al Failure check the PFC Rectifier Inverter fault Internal Failure check the Inverter Over temperature Check Function of the Fan or if something is blocking the Air Outlet Batt over volt Internal Fail...

Page 21: ...llow data transmission between a computer and the UPS unit The UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of powe...

Page 22: ...tion of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again the elec...

Page 23: ...e UPS unit to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be rest...

Page 24: ...JOVYATLAS POWERMASTER S 6000 P BAX 4469 E 24 14 Circuit diagram relay board...

Page 25: ...attery At the end of the bridging time the inverter switches off automatically and the consumers are no longer supplied with power When the mains power is restored the consumers begin again to be supp...

Page 26: ...UPS has to be recharged in case of UPS is being switched off totally after latest four weeks It is sufficient to connect the UPS to an input mains The recharging time shall be at least 8 hours We reco...

Reviews: