JOVYATLAS POWERMASTER S 6000-P BAX 4469 E
- 5 -
P L E A S E N O T E
!
In order to exclude the possibility of overloading or constant switching over to
bypass due to consumer generated non-sinusoidal current peaks, no devices
such as laser printers, fax machines as well as devices operating with a similar
technology should be connected to the UPS. In cases where it is essential that
such devices be operated then a UPS must be selected whose capacity can
match the maximum possible current peaks. Devices with power reduction due
to half wave power consumption, (e.g. coffee machines, hair dryers) can lead to
immediate destruction of the power-output stage. The battery is not galvanically
isolated from the mains so occurrence of a mains voltage at the battery terminals
is possible! The UPS unit does not have an output transformer and is therefore
not galvanically isolated from the mains!!
P L E A S E N O T E!
The batteries used are just designed for the required backup time at nominal
load. Operation of the UPS unit in free running mode for a longer period of
time on battery can damage the batteries. This effect is due to the nature of
the battery since for a longer discharge period the final discharging voltage is
not reached.
N O T E!
The UPS should be attached to the mains supply and switched on at the latest 4
weeks after receipt in order to prevent the battery discharging itself.
1
General Notes
The device may only be opened by trained specialists.
The system is to be connected up and earthed according to VDE regulations. Provisions of the local energy
– supply company must be observed.
The ventilation slits on the front and rear sides must not be covered and a distance from the wall of at least
100 mm
is essential.
The UPS unit is built according to Protection Class
IP 21
and is designed for installation in heated internal
spaces (at 20°C). A lower operating temperature lowers the bridging time.
No devices with a connecting cable in excess of
10 metres
in length should be connected to the UPS. This
measure serves to ensure observance of the EMC standard.
No alterations should be made to the UPS unit. The warranty will expire in cases of inappropriate physical
interventions.
2
Description of the System
Power supply devices of the model range JOVYATLAS POWERMASTER S are particularly suited for
supplying important power consumers in industry and the office such as personal computer, computer-
controlled devices, PLCs and similar equipment. The output voltage is sinusoidal. In normal cases the
attached consumers are supplied with power from the installed rectifier and installed inverter from the mains
power supply network (online operation). Any disturbances in the mains such as voltage peaks, voltage
drops, harmonic distortions or noises etc. are filtered out. The installed battery is constantly being charged