Wärtsilä JOVYSTAR COMPACT M
BAX 5480
- 84 -
17 Technical Data
JOVYSTAR COMPACT m
Online UPS-Type
60 kVA
80 kVA
100 kVA
125 kVA
160 kVA
Output
Output apparent power (cos φ = 1)
60 kVA
80 kVA
100 kVA
125 kVA
160 kVA
Output active power (cos φ = 1)
60 kW
80 kW
100 kW
125 kW
160 kW
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
- Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V / 3 x 400/230 V / 3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
50/60 Hz
±0,001 Hz
±2 Hz
Rated output current
87 A
115 A
144 A
180 A
231 A
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
< 1 %
< 5 %
Input Rectifier
Input voltage
3 x 400/230 V +15 % -20 %
Input frequency
50/60 Hz ±10 %
Input current (at 100 % load, without battery charging)
91 A
122 A
152 A
190 A
243 A
Input current (at 100 % load, max. battery current)
109 A
140 A
170 A
214 A
267 A
Input power factor (at 100 % load)
> 0,99
Input current THD (at 100 % load)
< 3 %
Input Bypass
Input voltage
3 x 380/220 V / 3 x 400/230 V / 3 x 415/240 V ±10 %
Input frequency
50/60 Hz ±10 %
Battery
Number of battery cells
360 - 372
Compensation charging voltage
817 V (2,27 V/Z) @ 360cells
Cut-off voltage
620 V (1,72 V/Z) @ 360cells
Max. battery charging current (at 100 % load)
15 A
15 A
15 A
20 A
20 A
Max. battery charging current with activated DCM
(
D
ynamic
c
harging
m
ode, only at partial load)
50 A
50 A
Battery charging characteristic
IU (DIN 41773)
Overload capability/Output short circuit characteristic
Overload capability inverter
> 100 % to 125 % for 10 min (1)
> 125 % to 150 % for 30 s
> 150 % to 199 % for 100 ms
Overload capability static bypass
150 % continuously
1000 % for 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
Current limitation to 100 ms
265 A
300 A
400 A
490 A
640 A
Short Circuit Current after 100ms up to 5seconds
130 A
172 A
216 A
270 A
346 A
Selectivity
½ cycle (fuse gG 20% In)
Design
Dimensions (W x H x D)
560 x 1800 x 940 mm
Weight (without battery)
250 kg
300 kg
320 kg
360 kg
380 kg
Paint
RAL 9005
Noise level
< 60 dB
protection degree
IP 20
Conformity according IEC 62040
Reference Standards
EN 62040 – 1, EN 62040 – 2, EN 62040 - 3
UPS classification
VFI SS 111
Other data
Efficiency normal mode (at 100 % load) (AC to AC)
> 95 %
Efficiency battery mode (at 100 % load) (DC to AC)
> 97 %
Efficiency eco-mode (Offline-mode)
> 98 %
Max. crest factor without power reduction
3 : 1
Heat dissipation (at 100 % load and rated input voltage)
3.2 kW
4.2 kW
5.3 kW
6.6 kW
8.4 kW
Requirements to the installation position
Max. installation altitude without power reduction
< 1000 m
Power reduction for installation altitude
according to IEC EN 62040-3
1 % every 100 m above 1000 m up to 2000 m
Required air cooling volume
1000 m³/h
1000 m³/h
1200 m³/h
1200 m³/h
1500 m³/h
UPS operating ambient temperature
0 to +40 °C
UPS storage temperature
-10 to +70 °C
Battery ambient -/storage temperature
(recommended battery ambient temperature,
see also battery operating instruction)
0 to +25 °C
+20 °C
Relative humidity (non condensing)
< 95 %
(1) For 160kVA Overload capability 10' >100%...110%, 5' >110…125%