Wärtsilä JOVYSTAR COMPACT S
BAX 5452
-
15 -
The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as much as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same installation conditions
apply as indicated in the table below.
Power (kVA)
30
40
50
L – mm
505
H – mm
1505
X (min.) - mm
0
Y (min.) – mm
500
A (min.) – mm
500*
*Only required at installed battery inside the UPS (Battery exchange)!
The table below shows the air volume required for an optimal ventilation and cooling of the UPS.
Power (kVA)
30
40
50
Air volume (m3/h)
900
900
1100