Wärtsilä JOVYSTAR COMPACT L
BAX 5624
- 19 -
Picture 5 – Clearances
The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as much as
possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same installation
conditions apply as indicated in the table below.
- UPS with internal batteries
A (mm) B (mm) C (mm)
D (mm)
Recommended clearances
50
1200
50
600
Minimum clearances
0
1200
0
400
The table below shows the air volume required for an optimal ventilation and cooling of the UPS.
Power (kVA)
200
Air volume (m3/h)
1800