Wärtsilä JOVYSTAR COMPACT L
BAX 5624
- 28 -
9.5.4 Remote emergency power off (EPO)
Auxiliary EPO contact on terminals X10-7/8.
The voltage supply to the loads can be interrupted from a remote location by using this contact (i.e. for
safety requirements). A normally closed contact is required; when this contact is open the static
inverter and by-pass switches are opened so that the output supply is interrupted.
In case the external EPO command is not provided short-circuit the terminals 7-8.
9.5.5 Battery auxiliary contact
Battery auxiliary contact on terminals X10-9/10.
This auxiliary contact is necessary to indicate the position of the isolator (open-closed).
9.5.6 Diesel Generator auxiliary contact
Auxiliary contact from the Diesel Generator on terminals X10-11/12.
A normally open contact must be used; the contact must close when the diesel generator is operating.
The microprocessor will acquire the status of the contact and, upon the rectifier start-up, it will enable
the "Diesel Mode" operation, that is the operation at reduced DC voltage in order to reduce the power
drawn from the AC line.
9.6 Serial interfaces and external connections
The UPS is provided with serial interfaces and external connection facilities for the communication of
the operating status and parameters.
Picture 8 – Position of the serial interfaces