Wärtsilä JOVYSTAR COMPACT L
BAX 5624
- 34 -
Picture 12 – Inverter start-up
3)
As the inverter is correctly started-up, close the bypass switch SBCB when indicated by the
display. The logic will check the correctness of the bypass phase sequence and RMS voltage
value.
Picture 13 – Bypass start-up
4)
Close the battery switch BCB when indicated by the display.