Wärtsilä JOVYSTAR COMPACT L
BAX 5624
- 36 -
Picture 16 – Start-up end
10.3 Shut-down procedure
1)
Open the switch
OCB
.
2)
Open the switch
BCB
.
3)
Open the switch
SBCB
.
4)
Open the switch
RCB
.
10.4 SWITCHING PROCEDURE TO MANUAL BYPASS
The load is transferred to Manual Bypass with no interruption of supply to the loads. In this configuration,
the system can be restarted via the return procedure from load on manual bypass, without the need to
de-energize the loads.
Manual bypass
To perform the switching procedure correctly, make sure no alarms are present on the system.
During Manual Bypass the load is supplied directly by the input mains, therefore continuous
supply cannot be guaranteed to the loads.
1)
Move the
Bypass_SW
selector to the
BYPASS
position.
2)
Close the switch
MBCB
.
3)
Open the switch
OCB
.
4)
Open the switch
BCB
.
5)
Open the switch
SBCB
.
6)
Open the switch
RCB
.