Wärtsilä JOVYSTAR COMPACT S
BAX 5452
-
35 -
CAN bus statistic static switch:
Number of received data and number of
correctly received data in percent
All UPS devices send data;
All UPS devices receive data
Sub menu
Display
Main menu
Parallel menu only visible, if the UPS
belongs to a parallel system!
POWER: All UPS devices supply the load
REX: X = Number of the UPS
devices in the parallel-standby mode
Digit = Device number in the parallel
system; M = Master, S = Slave;
? = No communication exists on the data
bus in the parallel system;
[ ] = Identify position/configuration of the
current UPS in the parallel system
Position of the current UPS in the parallel
system/Number of UPS devices in the
parallel system
PARALLEL
x / y
Possibility: Master/Slave
Only a master possible, or faults in the data
communication bus
PARALLEL
MASTER
PARALLEL
EXIT
INFO
PARALLEL
PARALLEL
1- S 2- M 3-[S] 4- ?
PARALLEL
REX
PARALLEL
CAN STATISTICS SSW
MSG RX: xxxxx xxx.x%
RESET
CAN bus inverter:
Number of received data and number of
correctly received data in percent
Only the master sends data;
Only the slaves receive data
PARALLEL
CAN STATISTICS INV
SYNC RX: xxxxx xxx.x%
CAN bus inverter:
Number of received data and number of
correctly received data in percent
All UPS devices send data;
All UPS devices receive data
PARALLEL
CAN STATISTIK INV
MSG RX: xxxxx xxx.x%
Display the modbus address
INFO
MODBUS
Settable address range: 1… 247
MODBUS
ADDRESS: xxx
RESET