Wärtsilä JOVYSTAR COMPACT S
BAX 5452
-
49 -
8 Appendix
The following pages contain technical documents, including drawings and technical specifications for the UPS
unit.
8.1 Technical data
JOVYSTAR COMPACT S
Online UPS-Type
30 kVA
40 kVA
50 kVA
Output
Output apparent power (cos φ = 0,9)
30 kVA
40 kVA
50 kVA
Output active power (cos φ = 1)
27 kW
36 kW
45 kW
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
- Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V / 3 x 400/230 V / 3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
50/60 Hz
±0,001 Hz
±2 Hz
Rated output current (cos φ = 0,9)
44 A
58 A
73 A
Rated output current (cos φ = 1,0)
39 A
52 A
65 A
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
< 1 %
< 5 %
Input rectifier
Input voltage
3 x 400/230 V +15 % -20 %
Input frequency
50/60 Hz ±10 %
Input current (at 100 % load, without battery charging)
42 A
56 A
70 A
Input current (at 100 % load, max. battery current)
54 A
66 A
88 A
Input power factor (at 100 % load)
> 0,99
Input current THD (at 100 % load)
< 3 %
Input Bypass
Input voltage
3 x 380/220 V / 3 x 400/230 V / 3 x 415/240 V ±10 %
Input frequency
50/60 Hz ±5 %
Battery
Number of battery cells
2 x 180
Compensation charging voltage
2 x 409 V (2,27 V/Z)
Cut-off voltage
2 x 310 V (1,72 V/Z)
Max. battery charging current (at 100 % load)
10 A
8 A
15
Battery charging characteristic
IU (DIN 41773)
Overload capability/Output short circuit characteristic
Overload capability inverter
< 125 % for 10 min
125 % to 150 % for 30 s
> 150 % for 100 ms
Overload capability static bypass
150 % continuously
1000 % for 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
1. Current limitation to 500 ms
2. Current limitation from 500 ms to 5 s
78 A
66 A
104 A
87 A
130 A
109,5 A
Design
Dimensions (W x H x D)
505 x 1505 x 940 mm
Weight (without battery)
140 kg
150 kg
190 kg
Weight (with battery)
500 kg
510 kg
550 kg
Paint
RAL 9005
Noise level
< 52 dB
< 57 dB
International protection
IP 20
Conformity according IEC 62040
EMV-class
C3
UPS classification
VFI SS 111
Other data
Efficiency normal mode (at 100 % load)
> 93 %
Efficiency battery mode (at 100 % load)
> 96 %
Efficiency eco-mode (Offline-mode)
> 98 %
Max. crest factor without power reduction
3 : 1
Heat dissipation (at 100 % load and rated input voltage)
2 kW
2,7 kW
3,4 kW
Requirements to the installation position
Max. installation altitude without power reduction
< 1000 m
Power reduction for installation altitude
according to IEC EN 62040-3
0,5 % every 100 m above
1000 m up to 2000 m
Required air cooling volume
900 m³/h
900 m³/h
1100 m³/h
UPS operating ambient temperature
0 to +40 °C
UPS storage temperature
-10 to +70 °C
Battery ambient -/storage temperature
(recommended battery ambient temperature,
see also battery operating instruction)
0 to +25 °C
+20 °C
Relative humidity (non condensing)
< 95 %