Wärtsilä JOVYSTAR COMPACT M
BAX 5480
- 25 -
Should larger cable cross-sections be required for the installation than the maximum cross-section of
the UPS terminals, a socket or a terminal box can be installed near the UPS. From there to the UPS, a
cable laying with a smaller cross-section can be possible (better laying conditions such as installation
type, cable length, ...).
Details of the electrical connections
Power (kVA)
60
80
100
125
160
Input fuses [A]
Rectifier
125
160
200
250
315
Bypass
125
160
200
250
315
Power connections
Type
Screw terminals
Conductor max. cross section [mm2]
35
70
95
Max. number of conductors
1
Tightening torque [Nm]
4 ÷ 4,5
7 ÷ 8
15 ÷ 20
PE
Bolt M10 (19 Nm)
Rated current (at full load and battery recharging)
Power (kVA)
60
80
100
125
160
Rectifier input [A]
(1)
109
140
170
214
267
Bypass input / Output [A]
(1) (2)
87
115
144
180
231
Battery [A]
100
133
166
208
266
(1)
Values referred to 400Vac rated voltage
(2)
For the overload values refer to the Technical Specification
9.2 Backfeed Protection Device
The UPS is provided (as option) with voltage-free contacts, which can be used to operate the shunt
trip coil (undervoltage release type) of the external sectioning device; the external device is not part of
the UPS supply and is provided and installed at customer care.
The following table shows the main electrical characteristics of the external sectioning device.
Backfeed protection device
Power (kVA)
60
80
100
125
160
Maximum operating voltage (Vac)
690
Minimum rated current (A)
125
160
200
250
315
Category
AC-1
A backfeed contactor can also be installed inside the UPS as an option.