Wärtsilä JOVYSTAR
– DELTA 40 – 150kVA BAX 4647E - 28 -
PASSWORD
Password entering; if wrong the main menu screen is shown. The password
is “123”, it is unchangeable. It shall notice the operator that deeper impacts
are going to be done.
000
SPECIAL MENU
Reset status of the UPS. It is used in case of a blocked retransfer. It is ac-
cessed pressing the
key, pressing the keys
or
the other sub-
menus are being displayed.
RESET
SPECIAL MENU
SETTINGS. This is used for setting the date and the time of the UPS internal
clock. It is accessed pressing the
key, pressing the keys
or
the
other sub-menus are being displayed.
SETTINGS
SPECIAL MENU
UPS TEST. This is for a short UPS test. It is accessed pressing the
key, pressing the keys
or
the other sub-menus are being displayed..
UPS TEST
SPECIAL MENU
BATTERY TEST. This is used for a battery test. It is accessed pressing the
key, pressing the keys
or
the other sub-menus are being dis-
played..
BATTERY TEST
SPECIAL MENU
Pressing the key
the main menu screen is shown, pressing the keys
or
the other sub-menus are being displayed.
EXIT
4.6.4.3.1
Reset
PRESS RESET
This menu provides a general reset of the UPS status pressing the key
RESET. Pressing another key exit the menu.
TO RESET UPS
4.6.4.3.2
Settings
This menu allows setting the internal clock of the UPS.
CLOCK SETTING
The numbers can be modified with the key
or
and they are confirmed
by pressing
key. Pressing the key RESET leads to the special menu.
25-12-01 18:48
4.6.4.3.3
Test UPS
PRESS RESET
Pressing the key RESET causes the commutation to bypass. After a certain
time the UPS will resume normal operation Pressing the key
leads to
the special menu.
FOR COMMUTATION