Wärtsilä JOVYSTAR
– DELTA 40 – 150kVA BAX 4647E - 5 -
Wärtsilä JOVYSTAR DELTA
Online UPS-Type
100 kVA
125 kVA
150 kVA
Output
Output apparent power (cos
φ = 0,8)
100 kVA
125 kVA
150 kVA
Output active power (cos
φ = 1)
80 kW
100 kW
120 kW
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
-
Tolerance dynamic load (0 % → 100 % → 0 %)
- Correction time after load step
3 x 400/230 V
±1 %
±2 %
±5 %
< 40 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
50/60 Hz
±0,001 Hz
±2 Hz
Rated output current (cos
φ = 0,8)
145 A
181 A
231 A
Rated output current (cos
φ = 1,0)
116 A
145 A
185 A
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
< 2 %
< 5 %
Input
Input voltage
3 x 400/230 V ±10 %
Input frequency
50 or 60 Hz ±5 %
Input current (at 100 % load, without battery charging)
160 A
200 A
256 A
Input current (at 100 % load, max. battery current)
200 A
250 A
325 A
Input power factor (at 100 % load)
> 0,8
Input current THD (at 100 % load)
< 30 %
Battery
Number of battery cells
192
Compensation charging voltage
436 V (2,27 V/Z)
Cut-off voltage
326 V (1,70 V/Z)
Max. battery charging current (at 100 % load)
40 A
40 A
50 A
Battery charging characteristic
IU (DIN 41773)
Overload capability/Output short circuit characteristic
Overload capability inverter
>100 % to 125 % for 10 min*
> 125 % to 150 % for 1 min
> 150 % to 200 % for 100 ms
*150 kVA: >100 % to 125 % for 2 min 30 s
Overload capability static bypass
150 % steady
200 % for 1 min
Short circuit current
232 A
290 A
290 A
Short circuit characteristic
1. Current limitation to 200 % for 100 ms
2. Current limitation to 125 % for another 5 s
3. Shutdown of the inverter for 30 min
Design/Conformity
Dimensions (W x H x D)
815 x 1670 x 820 mm
Weight (without battery)
813 kg
853 kg
905 kg
Paint
RAL 5026 / RAL 9006
Noise level
< 59 dB
EMV-class according to IEC EN 62040-2
C3
Class of protection according to IEC EN 62040-3
1
International protection
IP 20
Other data
Efficiency normal mode (at 100 % load)
> 92 %
Efficiency battery mode (at 100 % load)
> 94 %
Max. crest factor without power reduction
3 : 1
Heat dissipation
(at 100 % load and rated input voltage)
6,9 kW
5934 kcal/h
8,7 kW
7482 kcal/h
11,1 kW
9546 kcal/h
Requirements to the installation position
Max. installation altitude without power reduction
< 1000 m
Power derating for installation at altitudes higher than
1000m according to IEC EN 62040-3
1 % each 100 m > 1000 m up to max.. 5000 m
Minimum distance between UPS and wall
100 mm
Required air cooling volume
2500 m³/h
2500 m³/h
3300 m³/h
UPS operating ambient temperature
0 to +40 °C
UPS storage temperature
-10 to +70 °C
Battery ambient temperature
(recommended battery ambient temperature,
see also battery operating instruction)
0 to +25 °C
+20 °C
Battery storage temperature
0 to +25 °C
Relative humidity (non condensing)
< 95 %