Wärtsilä JOVYTEC L 6kVA
– 10kVA BAX 3297_en
- 25 -
7.3
Configuration
Use of the function display and the function keys allows diverse settings to be made on the UPS unit. The
formalism is as follows:
-
In order to achieve Configuration Mode it is necessary to press the key
FUNC
for 2 seconds. The first
configuration parameter appears in the display.
-
The key
FUNC
is used to manoeuvre through the parameters.
-
The key
ENTER
is used to select the parameter point to be altered.
-
The key
FUNC
is used to move through the options for the selected parameter.
-
The key
ENTER
is used to confirm the selected option and the display readout:
Save ?
appears before
hand
-
Saving is achieved by pressing the key
ENTER
again.
7.4
Table of parameters
Adjustable
parameter
Indication in
the display
Explanation
Selections
for
parameter
Factory
setting
Adjusting the output voltage
O/P V adjustment
Nominal voltage
208/220/
230/240V
230V
Setting the
input frequency tolerance
I/P Freq. Adjustment
Frequency tolerance in
unsynchronised mode
± 2%
± 5%
± 7%
± 5%
Setting of the tolerance of the bypass
voltage
I/P bypass adjustment
Voltage tolerance
± 10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
Free-Run-Set
Unsynchronised mode
ON/OFF
ON
Bypass activation/deactivation in Free
Run Mode
Free
–Run-Mode
If activated the UPS will switch
to bypass if the preset
parameters are not maintained
ON/OFF
OFF
Operating mode setting
HE mode setting
Online/Offline mode
ON/OFF
OFF
Setting for a permanent manual bypass Man. bypass setting
Activate manual bypass (only
for servicing)*
ON/OFF
OFF
Load management
Load segment setting
Segment 1 ON/OFF
Segment 2 ON/OFF
ON/OFF
ON
Performing a battery test
Manual battery test
Battery test
Battery OK.
Battery not OK.
ON/OFF
OFF
Quiet functioning
Alarm acoustic
Activate, deactivate the
acoustic alarm
ON/OFF
OFF
Number of battery packs
No. of ext. batteries
Setting number of battery
packs for the autonomy
calculation; a maximum of 2
1 - 2
Dependent on
the required
bridging time
Reversal polarity protection
Phase reversal setting
Activation, deactivation
of phase reversal
ON/OFF
OFF
Language selection
Language
Language selection
English
German
French
Spanish
Italian
German
Generator mode
Generator
Generator mode**
ON/OFF
OFF
Setting RS 232 interface
COM control command
Setting of RS232 interface
ON/OFF
ON
*)
The manual bypass function should always be switched off since for a switched on manual bypass the load in the case of a
power failure cannot be supplied by the UPS.
**)
The UPS should we switched off and then switched on again before the generator is switched.
P L E A S E N OT E!
If the selected option is not stored within 10 seconds then the value is reset
automatically and the menu goes bank into its normal condition.