Notes on Maintenance
If the Ups is switched off for more than 4 weeks, the batteray has to be recharged. It is accomplished by simply
connecting the UPS to an input mains. The charging time shall be at least 8 hours, we recommend a recharging
time of 24 hours.
The standard battery is maintenance free. In case of using a customized battery consult the battery
manufacturer.
The air-inlets/outlets on the front and rear side must be kept free of dirt and dust. A distance to a wall must be
guaranteed at a minimum of 100mm.
The overall function of the UPS shall be verified by switching off the input mains when having (only non-critical
loads applied).
If the UPS cannot be checked regularly, we strongly recommend any remote supervision facility.
The lifetime of the fans is typically about 20.000h. We strongly recommend an exchange in the right time.
A T T E N T I O N !
All kind of maintenance and/or servicing may be carried out by authorized
personnel only. The UPS has to be isolated.