Wärtsilä JOVYTEC P 700VA
– 3kVA
BAX 3345
- 31 -
13.
Battery Cabinets
13.1
Technical Data / Autonomy Times
For longer autonomy of ups systems are additional battery cabinets necessary. The available cabinets
for the ups systems are described in the following table:
UPS
Time
[min]
Battery
Cabinet
Dimensions
W x H x D [mm]
Battery Cabinet
Weight [kg]
UPS and Battery Cabinet
Weight [kg]
JOVYTEC P 700
0
-
-
-
8,4
JOVYTEC P 700
10
-
-
-
13,6
JOVYTEC P 700
35
BM1
152 x 238 x 420
30
38,4
JOVYTEC P 700
65
BM2
225 x 360 x 425
40
50,4
JOVYTEC P 1000
0
-
-
-
9,4
JOVYTEC P 1000
10
-
-
-
17,2
JOVYTEC P 1000
25
BM1
152 x 238 x 420
30
39,4
JOVYTEC P 1000
45
BM1
152 x 238 x 420
40
57,2
JOVYTEC P 1000
60
BM2
225 x 360 x 425
50
59,4
JOVYTEC P 1000
120
BM3
280 x 680 x 630
80
91,9
JOVYTEC P 1500
0
-
-
-
10,4
JOVYTEC P 1500
6
-
-
-
18,2
JOVYTEC P 1500
30
BM1
152 x 238 x 420
40
58,2
JOVYTEC P 1500
40
BM2
225 x 360 x 425
50
60,4
JOVYTEC P 1500
60
BM3
280 x 680 x 630
80
92,9
JOVYTEC P 1500
95
BM3
280 x 680 x 630
100
112,9
JOVYTEC P 2000
0
-
-
-
16,2
JOVYTEC P 2000
8
-
-
-
31,8
JOVYTEC P 2000
15
BM2
225 x 360 x 425
50
66,2
JOVYTEC P 2000
30
BM2
225 x 360 x 425
50
66,2
JOVYTEC P 2000
60
BM3
280 x 680 x 630
90
106,2
JOVYTEC P 2000
80
BM3
280 x 680 x 630
110
129,2
JOVYTEC P 2000
120
B10ES
520 x 1200 x 790
230
249,2
JOVYTEC P 3000
0
-
-
-
17
JOVYTEC P 3000
5
-
-
-
32,6
JOVYTEC P 3000
15
BM2
225 x 360 x 425
50
67
JOVYTEC P 3000
25
BM2
225 x 360 x 425
60
77
JOVYTEC P 3000
35
BM3
280 x 680 x 630
90
107
JOVYTEC P 3000
50
BM3
280 x 680 x 630
110
130
JOVYTEC P 3000
60
B10ES
520 x 1200 x 790
200
220
JOVYTEC P 3000
85
B10ES
520 x 1200 x 790
250
270
Table Battery Cabinets