Replacing an internal UPS battery
UPS units of the type JOVYATLAS POWERMASTER S 6000
offer the option of replacing the battery while
operating. One must ensure in this case that the UPS unit is running in normal mode and not in autonomy
mode. Proceed as follows to replace the battery:
1. Remove the battery pack.
2. Open the battery pack by using a Phillips Screw Driver.
3. Exchange the batteries. Please take attention to, that there is still a high dc – voltage inside the
battery pack, so only qualified personel is allowed to exchange the battery.
4. Screw the battery pack together again using the cross-head screws.
5. Push the battery pack into the battery jack of the UPS unit.
6. Conduct a manual battery test to check the battery.
Please note that when conducting the battery test
faulty insertion of the battery could mean that the load is not taken over and this will lead to power
consumer crashes.
P L E A S E N O T E!
The following works to the unit may only be performed by trained personnel and with
the UPS unit in a deenergised condition and in accordance to the electrical safty
regulations.
Observe the relevant safety regulations!!