Fig 9-10
Electric pre-heating unit, main dimensions
Mass [kg] (wet)
B [mm]
H [mm]
L [mm]
Heating power
[kW]*
93
460
800
1050
12 (16)
95
460
800
1250
16 (21)
95
460
800
1250
18 (24)
103
480
840
1250
24 (32)
125
480
840
1250
32 (42)
9.3.13
Throttles
Throttles (orifices) are to be installed in all by-pass lines to ensure balanced operating conditions
for temperature control valves. Throttles must also be installed wherever it is necessary to
balance the waterflow between alternate flow paths.
9.3.14
Thermometers and pressure gauges
Local thermometers should be installed wherever there is a temperature change, i.e. before
and after heat exchangers etc.
Local pressure gauges should be installed on the suction and discharge side of each pump.