20
Installation manual
6.4
Shared exhaust duct
It is recommended that each machine is connected to a separate exhaust duct.
When several machines shall use the same exhaust duct the exhaust duct must increase after each machine. The
recommended diameter increase progression is the one in the table.
If several machines are installed on the same exhaust pipe, it is recommended to adjust the airflow on the machines
when all machines are started and running a program with no heat.
Please consider that unnecessarily large ducts create issues with the draught.
Number of machines
1
2
3
4
5
6
7
8
9
10
Exhaust duct
⌀
mm
200
315
400
400
500
500
630
630
630
800
Recommended area
of fresh air intake
m
2
0.16
0.39
0.63
0.63
0.98
0.98
1.56
1.56
1.56
2.51
Minimum area of
fresh air intake
Gas heated/Electric
heated
m
2
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
Minimum area of
fresh air intake
Steam heated
m
2
0.039
0.078
0.117
0.156
0.195
0.234
0.273
0.312
0.351
0.39
The exhaust duct diameter must not be reduced.
6.5
Exhaust dimensioning
It is important that the machine has correct air volume compared to each machines power.
If the air flow is smaller or larger this will result in a longer drying period.
If the outlet pipe is long or the ventilation is not properly designed we recommend to clean the outlet pipes periodi-
cally. Usually, longer ducts need more frequent cleaning.
The exhaust pipes shall be short in order for the machine to work in the best way.
All cover panels must be mounted in order for the machine to work in the best way.
Summary of Contents for D7-550
Page 1: ...Installation manual Tumble dryer D7 550 Type N2 Original instructions 438905413 EN 2023 02 27...
Page 2: ......
Page 4: ......
Page 42: ......
Page 43: ......