Engineering Guide Specifi cations

PART 1 - GENERAL

SUMMARY

The liquid source, water-to-water heat pump shall be 
a single packaged, reverse-cycle heating/cooling unit.  
Each unit shall contain microprocessor control for two 
hermetically sealed, scroll compressors with brazed plate 
heat exchangers and thermostatic expansion valves.

PERFORMANCE REQUIREMENTS
Fluid Temperature Performance:

Heat Pump shall be capable of continuous operation over the 
entire range of entering source-fluid temperature of -1°C – 
43°C in cooling mode and -1°C – 32°C in heating mode.

Heat Pump shall be capable of continuous operation over 
the entire range of entering load conditions as indicated in 
the engineering performance tables.

SUBMITTALS

Product submittal data shall contain manufacturer’s 
specifications for heat pumps showing dimensions, weights, 
capacities, performance ratings, electrical characteristics, 
gauges and finishes of materials and installation instructions.

Submit internal electrical wiring diagrams
Submit Control Diagrams and Specifications

QUALITY ASSURANCE

Liquid source, water-water heat pumps shall be tested, rated, 
and certified in accordance with the following standards.  

• 

ASHRAE 15 for safety code for mechanical refrigeration.

• 

ASHRAE 147 for refrigerant leaks, recovery, and 
handling and storage requirements.

• 

ASHRAE 90.1 – minimum Energy Efficiency compliance 
for water-to-water heat pumps.

• 

Comply with NFPA 70 or National Electric Code (N.E.C)

• 

Comply with UL 1995 and be nationally recognized 
with ETL

• 

Tested in accordance with EN14511 13256-2

Each unit shall be run tested at the factory using water. 
Quality control system shall automatically perform via 
computer: triple leak check, pressure tests, evacuate and 
accurately charge system, perform detailed heating and 
cooling mode tests, and quality cross check all operational 
and test conditions to pass/fail criteria. Units tested without 
water flow are not acceptable. 

WARRANTY

Standard Warranty: The units shall be warranted by the 
manufacturer against defects in materials and workmanship 
for a period of 12 months from startup or 18 months
from shipment. 

Special Warranty:  Manufacturer's standard form in which 
manufacturer agrees to repair or replace components 
of chillers that fails in materials or workmanship within 
specified warranty period.

Extended warranties include, but are not limited to,
the following:
• 

Complete heat pump including refrigerant and oil charge.

• 

Complete compressor and drive assembly.

• Parts 

only.

PART 2 - PRODUCTS

WATER TO WATER HEAT PUMP EQUIPMENT

Heat pump equipment shall be factory assembled with 
two refrigerant circuits consisting of scroll compressors, 
brazed-plate heat exchangers for the evaporator and 
condenser, microprocessor controls, and safety devices 
such as refrigerant pressure switches.  Units must be 
field installed with a minimum of a differential waterside 
pressure switch or flow proving switch on the outlet of the 
load and source piping.

Frame & Enclosure

Frame shall be constructed of 10 gauge welded steel with 
forklift pockets in the bottom channel and threaded weld 
nuts for lifting points in the top of the frame.

Enclosure shall be factory installed and constructed of 
heavy-gauge G60 galvanized steel coated with polyester 
powder coat paint.  Paint shall be rated for 1,000 hour 
of salt spray using ASTM B117.  Panels, other than control 
service door, shall be lined with 50.8mm inch thick, glass 
fiber glass insulation with an foil face, washable backing.

Compressor:

1. 

Hermetically sealed, scroll compressors with factory 
charged POE or PVE oil.

2. 

Suction gas cooled motors operate at 3500 rpm 
protected by internal overload device.  Model sizes 150 
protected by external compressor protection module. 

3. 

Brazed connections to system piping utilizing braided 
stainless steel vibration absorbers  on all suction and 
discharge piping to mitigate vibration.

4. 

Compressors can be operated separately to provide 
staged capacity for lighter load conditions.

5. 

Factory mounted with rubber isolation grommets.

6. 

Acoustically insulated sound blankets are factory 
installed around the compressor to reduce sound 
emanating from the compressor.

Summary of Contents for ENVISION 2 NKW 030

Page 1: ...NKW 30 TO 150 KW Commercial Reversible Chiller 50 Hz Submittal Data English Language IP Metric Units SD2552WNB 09 16...

Page 2: ...Vintage Factory Use Non Standard Options SS Standard Future N None Future N None HydroLink Aurora Control Option A Standalone B BACnet C LonWorks Chassis E Enclosed Rev 29 April 2016 Vintage Factory U...

Page 3: ...ween the parties but are merely WaterFurnace s opinion or commendation of its products The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Uni...

Page 4: ...50 118 8 3 60 32 9 179 0 4 80 37 1 107 4 2 90 37 4 145 5 4 20 35 0 162 8 4 00 40 8 All ratings based upon 380 400V operation 10 7 14 All ratings based on new heat pump with clean heat exchangers Cooli...

Page 5: ...gain between the parties but are merely WaterFurnace s opinion or commendation of its products The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project...

Page 6: ...rmation contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely WaterFurnace s opinion or commendation of its products The latest versio...

Page 7: ...his document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 7 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Vibration Isolators 70 16 16...

Page 8: ...ment is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 8 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Physical Data Model Compressor Refri...

Page 9: ...Module An electronic protection module is provided with com pressors utilized in model size 150 This module will protect against phase reversal and phase loss at start up Protection is active for 5 se...

Page 10: ...wn is used for geothermal open loop well water systems with a minimum of 10 C EST The middle flow rate shown is the minimum geothermal closed loop flow rate The highest flow rate shown is optimum for...

Page 11: ...example given Antifreeze Correction Antifreeze Type Antifreeze by wt Heating Cooling Pressure Drop Load Source Load Source EWT F C 90 32 2 30 1 1 50 10 90 32 2 30 1 1 Water 0 1 000 1 000 1 000 1 000...

Page 12: ...version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 12 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Pressure Drop...

Page 13: ...3 3 3 0 5 7 1 9 15 22 6 41 4 6 4 35 1 6 5 5 6 20 2 41 7 6 1 35 6 6 8 5 5 19 0 42 0 5 9 36 1 7 1 5 5 25 32 2 39 2 8 4 30 8 4 7 6 1 30 0 39 6 8 1 31 5 4 9 6 1 28 8 40 0 7 8 32 2 5 1 6 0 40 46 8 37 0 10...

Page 14: ...1 23 6 51 4 5 7 57 1 30 9 15 4 24 7 55 4 5 6 61 0 33 5 15 8 20 1 3 10 4 2 31 7 6 6 38 2 16 5 27 0 5 9 33 1 6 9 40 0 16 3 27 3 6 7 34 6 7 3 41 9 16 2 27 7 20 12 1 43 4 7 1 50 5 20 9 29 2 14 5 43 5 7 4...

Page 15: ...5 7 2 8 15 22 2 57 7 8 9 48 7 6 5 5 9 19 9 58 2 8 6 49 5 6 7 5 8 18 7 58 7 8 4 50 3 7 0 5 7 25 31 9 55 1 11 4 43 7 4 8 6 3 29 7 55 7 11 0 44 6 5 0 6 2 28 5 56 2 10 7 45 6 5 3 6 1 40 46 6 52 5 13 9 38...

Page 16: ...32 9 15 4 25 2 76 5 8 2 84 7 31 8 15 3 20 1 9 10 4 3 45 5 9 2 54 7 16 8 26 9 6 0 47 3 9 3 56 6 17 4 27 1 6 9 49 1 9 3 58 4 17 9 27 3 20 12 2 62 2 10 0 72 2 21 1 29 0 14 6 63 4 10 1 73 6 21 4 29 2 15...

Page 17: ...2 11 2 63 0 6 6 6 1 19 7 74 6 10 8 63 7 6 9 6 0 18 5 75 0 10 5 64 4 7 1 6 0 25 31 7 70 4 14 5 55 9 4 8 6 5 29 5 71 4 14 5 57 0 4 9 6 4 28 4 72 4 14 4 58 1 5 0 6 4 40 46 3 66 6 17 9 48 7 3 7 6 9 44 3 6...

Page 18: ...81 4 10 4 91 8 26 7 14 3 30 21 5 89 4 10 8 100 1 28 4 14 7 24 4 89 9 10 9 100 8 28 2 14 7 25 8 90 4 11 0 101 4 28 0 14 7 20 2 5 10 4 3 59 8 12 5 72 3 16 3 26 9 6 1 62 8 12 6 75 5 17 0 27 2 6 9 65 8 12...

Page 19: ...8 96 6 6 7 6 0 18 5 112 8 16 4 96 4 6 9 6 0 25 31 7 107 3 22 1 85 2 4 9 6 4 29 5 107 2 21 5 85 7 5 0 6 4 28 4 107 2 21 0 86 3 5 1 6 4 40 46 3 100 5 26 9 73 6 3 7 6 9 44 2 101 0 26 2 74 8 3 9 6 9 43 2...

Page 20: ...0 16 7 153 7 27 9 14 8 20 3 8 10 4 6 86 3 18 9 105 2 15 6 26 6 6 2 90 6 19 2 109 8 16 1 26 9 7 0 94 9 19 4 114 3 16 7 27 2 20 12 9 113 7 20 6 134 3 18 9 28 4 15 1 117 5 20 9 138 4 19 2 28 7 16 2 121...

Page 21: ...45 8 154 4 42 4 112 0 3 6 7 2 43 9 157 0 40 8 116 1 3 8 7 1 43 0 159 5 39 2 120 2 4 1 7 0 50 55 5 146 4 49 4 97 0 3 0 7 6 53 6 145 1 47 1 98 1 3 1 7 5 52 7 143 9 44 8 99 1 3 2 7 5 12 6 15 21 7 178 1...

Page 22: ...4 6 20 6 3 10 4 8 138 5 31 00 169 5 15 2 26 4 6 2 150 4 31 9 182 2 16 1 26 9 6 9 162 2 32 8 195 0 16 9 27 4 20 13 2 180 1 33 71 213 8 18 2 28 1 15 2 190 9 34 7 225 6 18 8 28 5 16 2 201 7 35 7 237 4 19...

Page 23: ...Use 1 2 3 4 5 ON OFF FutureUse Acc 2 Dip 1 Acc 2 Dip 2 SeeFigure 1 for DHW wiring Current Transducer CT Thermistor Light emitting diode Green Relay coil Capacitor w bleed resistor Switch Condensate ov...

Page 24: ...EPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT CT2 4 3 CT2...

Page 25: ...agePCB traces Junction Quick connect terminal Wire nut Fieldwire lug Ground Fuse Legend Relay Contacts N O N C G T 1 3 2 P L1 Breaker CC Compressor Contactor FP1 Freeze Protection FP2 Freeze Protectio...

Page 26: ...door Unit Power Supply L1 L2 L3 L2 L1 L3 G Di sconnect fus ed disc onnect op onal F1 F2 F3 L1 L2 L3 L2 L1 L3 F7 F8 F9 Comp 1 Fuses Comp 2 Fuses Black G White H Red J Compressor A CCA T1 L1 T2 L2 T3 L...

Page 27: ...The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 27 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Wiri...

Page 28: ...the factory using water Quality control system shall automatically perform via computer triple leak check pressure tests evacuate and accurately charge system perform detailed heating and cooling mod...

Page 29: ...trol Panel 1 Factory installed wired and functionally tested at factory before shipment 2 Single point power connection to non fused or fused rotary type disconnect in control panel 3 Factory installe...

Page 30: ...Install anchor bolts to elevations required for proper attachment to supported equipment Maintain manufacturer s recommended clearances for service and maintenance Charge chiller with refrigerant and...

Page 31: ...s that the equipment is acceptable under the provisions of the job speci cation Statements and other information contained herein are not express warranties and do not form the basis of any bargain be...

Page 32: ...of any bargain between the parties but are merely WaterFurnace s opinion or commendation of its products The latest version of this document is available at www waterfurnace com Contractor P O Enginee...

Reviews: