WaterFurnace works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Please contact WaterFurnace at 1-888-929-2837 for latest design and
specifi cations. Purchaser’s approval of this data set signifi es that the equipment is acceptable under the provisions of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the
basis of any bargain between the parties, but are merely WaterFurnace’s opinion or commendation of its products. The latest version of this document is available at www.waterfurnace.com.
Contractor: P.O.:
Engineer:
Project Name:
Unit Tag:
SD2552WNB 09/16
12
Page _____ of _____
ENVISION
2
NKW
REVERSIBLE CHILLER - 50Hz
Pressure Drop
Note: Pressure drop is the same for load and source heat exchangers at 30°F fluid temperature.
Model
L/s
Pressure Drop (kPa)
0°C
10°C
20°C
30°C
45°C
030
1.3
5.5
4.8
4.1
4.1
3.4
1.9
14.5
13.1
12.4
11.7
10.3
2.5
22.8
21.4
20.0
19.3
17.2
045
1.9
6.3
5.5
5.1
4.9
4.0
2.8
15.9
14.8
13.8
13.4
12.4
3.8
25.7
24.1
23.0
22.1
20.1
060
2.5
8.9
8.2
7.9
7.5
6.6
3.8
21.7
20.7
20.0
19.3
17.9
5.1
34.3
32.6
31.4
30.6
28.6
090
3.8
8.6
7.9
7.4
6.9
6.1
5.7
21.0
20.0
19.3
18.6
16.5
7.6
32.9
31.4
30.3
29.6
27.2
150
6.3
19.0
17.6
16.5
15.4
14.0
9.5
32.4
31.0
30.3
27.8
26.8
12.6
43.9
42.5
41.8
39.3
38.3
10/7/14