ENVISION

2

 NKW

REVERSIBLE CHILLER - 50Hz

Engineering Guide Specifi cations cont.

Heat Exchangers:

1. 

The water to refrigerant heat exchangers shall be 
dual circuit, copper-brazed 316 stainless steel channel 
plates, capable of withstanding 4.5MPa psig working 
pressure on the refrigerant side and 3.1MPa psig on 
the water side. Refrigerant circuits are separate with a 
common water supply.  This provides optimal part load 
efficiency compared to using two single circuit heat 
exchangers.  Heat exchangers are designed to work as 
an evaporator and condenser. 

2. 

Heat exchangers are covered with 19mm closed-cell 
insulation on sizes 030-060 and 25mm closed-cell 
insulation on sizes 090-150.

3. 

Water line connections attached to the heat 
exchangers are groove type are factory installed 
with groove coupling and steel pipe nipple.  Pipe 
nipple is insulated and comes with 1/4" NPT pressure/
temperature port.

Refrigerant Components:

1. 

Unit shall utilize R-410A refrigerant type.  All system 
components shall be rated to appropriate UL standards 
to handle maximum system pressure. 

2. 

Factory charged, sealed system contains optimal 
refrigerant quantity.

3. 

Each refrigerant circuit shall utilize a thermostatic 
expansion valve (TXV) with stainless steel sensing bulb 
and laser welded diaphragm. TXV will control adequate 
superheat over the stated operating range as indicated 
in submittal data.  

4. 

Bidirectional, liquid line filter driers are to be factory 
installed to provide additional system cleanliness. 

5. 

Factory installed service ports for high and low 
pressure readings.

6. 

Optional factory installed pressure gauges mounted 
below control panel aid in field diagnostics and 
reduces need for technician applied gauges.

Control Panel

1. 

Factory installed, wired, and functionally tested at 
factory before shipment.

2. 

Single-point power connection to non-fused, or fused 
rotary-type disconnect in control panel.

3. 

Factory installed, DIN mounted CUBEFuse with Class J 
rating wired for protection of each compressor. 

4. 

Low voltage, emergency stop button factory wired and 
mounted to control panel service door.

5. 

Factory mounted class 2, control power transformer 
provides nominal 24 VAC low voltage power supply. 
Primary to transformer is protected by Class CC fuses.

6. 

High pressure cut out set at 4.1MPa with manual reset.

7. 

Low pressure cut out set at 275kPa with manual reset.

8. 

Unit shall have phase loss/reversal for
compressor protection.

Controls:

1. 

The unit shall be controlled using a microprocessor 
which sequences all functions and modes of operations.  

2. 

Units shall be capable to communicate thru standard 
DDC protocols such as N2, Lon, and BACnet (MS/TP @ 
19,200 Baud Rate).  

3. 

Standalone, non-communicating units are also 
available that will operate with thermostat, mechanical, 
or electronic signals.  Temperature set mode is capable 
of controlling to leaving/entering load temperature.

4. 

The control system shall have the following features:
• 

Anti-short cycle time delay of 5 minutes on 
compressor operation.

• 

Random start on power up mode

• 

Low voltage protection

• 

High voltage protection

• 

Unit shut down on high or low refrigerant pressures

• 

Unit shut down for freeze detection

• 

Source and Load heat exchanger freeze detection 
setpoint selectable for water or antifreeze

• 

Automatic intelligent reset

5. 

A 4 x 20 digit backlit LCD to display the following:
• 

Entering and leaving water temperatures

• 

High pressure, low pressure, low voltage, high 
voltage, freeze detection setpoint, and control status

• 

The low pressure shall not be monitored for 
the first 120 seconds after a compressor start 
command to prevent nuisance safety trips

• 

Remote fault indication on the thermostat

• 

An accessory relay output tied to each compressor 
selectable for normally open or normally closed

6. Control 

Inputs:

• Start/Stop
• Lead/Lag
• 

Freeze detection set point for load/source

• 

Water temperature set point

• Control 

Outputs:

• Status: 

Cooling/Heating/On/Off

• 

Load Side Supply and Return Temperatures

• 

Source Side Supply and Return Temperatures

• 

Evaporator Entering Refrigerant Temperatures

• 

Condenser Leaving Refrigerant Temperatures

Accessories:

1. 

Additional Items Not Listed Previously:
• 

Compressor sound blankets to reduce sound 
power level of unit. 

• 

Flow switch to monitor the units presence of flow.  

2. 

Flow Proving Switch
• 

A flow proving switch shall be available utilizing 
high reliability flow sensing technology.

Summary of Contents for ENVISION 2 NKW Series

Page 1: ...NKW 30 TO 150 KW Commercial Reversible Chiller 50 Hz Submittal Data English Language IP Metric Units SD2552WNB 09 16...

Page 2: ...Vintage Factory Use Non Standard Options SS Standard Future N None Future N None HydroLink Aurora Control Option A Standalone B BACnet C LonWorks Chassis E Enclosed Rev 29 April 2016 Vintage Factory U...

Page 3: ...ween the parties but are merely WaterFurnace s opinion or commendation of its products The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Uni...

Page 4: ...50 118 8 3 60 32 9 179 0 4 80 37 1 107 4 2 90 37 4 145 5 4 20 35 0 162 8 4 00 40 8 All ratings based upon 380 400V operation 10 7 14 All ratings based on new heat pump with clean heat exchangers Cooli...

Page 5: ...gain between the parties but are merely WaterFurnace s opinion or commendation of its products The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project...

Page 6: ...rmation contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely WaterFurnace s opinion or commendation of its products The latest versio...

Page 7: ...his document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 7 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Vibration Isolators 70 16 16...

Page 8: ...ment is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 8 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Physical Data Model Compressor Refri...

Page 9: ...Module An electronic protection module is provided with com pressors utilized in model size 150 This module will protect against phase reversal and phase loss at start up Protection is active for 5 se...

Page 10: ...wn is used for geothermal open loop well water systems with a minimum of 10 C EST The middle flow rate shown is the minimum geothermal closed loop flow rate The highest flow rate shown is optimum for...

Page 11: ...example given Antifreeze Correction Antifreeze Type Antifreeze by wt Heating Cooling Pressure Drop Load Source Load Source EWT F C 90 32 2 30 1 1 50 10 90 32 2 30 1 1 Water 0 1 000 1 000 1 000 1 000...

Page 12: ...version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 12 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Pressure Drop...

Page 13: ...3 3 3 0 5 7 1 9 15 22 6 41 4 6 4 35 1 6 5 5 6 20 2 41 7 6 1 35 6 6 8 5 5 19 0 42 0 5 9 36 1 7 1 5 5 25 32 2 39 2 8 4 30 8 4 7 6 1 30 0 39 6 8 1 31 5 4 9 6 1 28 8 40 0 7 8 32 2 5 1 6 0 40 46 8 37 0 10...

Page 14: ...1 23 6 51 4 5 7 57 1 30 9 15 4 24 7 55 4 5 6 61 0 33 5 15 8 20 1 3 10 4 2 31 7 6 6 38 2 16 5 27 0 5 9 33 1 6 9 40 0 16 3 27 3 6 7 34 6 7 3 41 9 16 2 27 7 20 12 1 43 4 7 1 50 5 20 9 29 2 14 5 43 5 7 4...

Page 15: ...5 7 2 8 15 22 2 57 7 8 9 48 7 6 5 5 9 19 9 58 2 8 6 49 5 6 7 5 8 18 7 58 7 8 4 50 3 7 0 5 7 25 31 9 55 1 11 4 43 7 4 8 6 3 29 7 55 7 11 0 44 6 5 0 6 2 28 5 56 2 10 7 45 6 5 3 6 1 40 46 6 52 5 13 9 38...

Page 16: ...32 9 15 4 25 2 76 5 8 2 84 7 31 8 15 3 20 1 9 10 4 3 45 5 9 2 54 7 16 8 26 9 6 0 47 3 9 3 56 6 17 4 27 1 6 9 49 1 9 3 58 4 17 9 27 3 20 12 2 62 2 10 0 72 2 21 1 29 0 14 6 63 4 10 1 73 6 21 4 29 2 15...

Page 17: ...2 11 2 63 0 6 6 6 1 19 7 74 6 10 8 63 7 6 9 6 0 18 5 75 0 10 5 64 4 7 1 6 0 25 31 7 70 4 14 5 55 9 4 8 6 5 29 5 71 4 14 5 57 0 4 9 6 4 28 4 72 4 14 4 58 1 5 0 6 4 40 46 3 66 6 17 9 48 7 3 7 6 9 44 3 6...

Page 18: ...81 4 10 4 91 8 26 7 14 3 30 21 5 89 4 10 8 100 1 28 4 14 7 24 4 89 9 10 9 100 8 28 2 14 7 25 8 90 4 11 0 101 4 28 0 14 7 20 2 5 10 4 3 59 8 12 5 72 3 16 3 26 9 6 1 62 8 12 6 75 5 17 0 27 2 6 9 65 8 12...

Page 19: ...8 96 6 6 7 6 0 18 5 112 8 16 4 96 4 6 9 6 0 25 31 7 107 3 22 1 85 2 4 9 6 4 29 5 107 2 21 5 85 7 5 0 6 4 28 4 107 2 21 0 86 3 5 1 6 4 40 46 3 100 5 26 9 73 6 3 7 6 9 44 2 101 0 26 2 74 8 3 9 6 9 43 2...

Page 20: ...0 16 7 153 7 27 9 14 8 20 3 8 10 4 6 86 3 18 9 105 2 15 6 26 6 6 2 90 6 19 2 109 8 16 1 26 9 7 0 94 9 19 4 114 3 16 7 27 2 20 12 9 113 7 20 6 134 3 18 9 28 4 15 1 117 5 20 9 138 4 19 2 28 7 16 2 121...

Page 21: ...45 8 154 4 42 4 112 0 3 6 7 2 43 9 157 0 40 8 116 1 3 8 7 1 43 0 159 5 39 2 120 2 4 1 7 0 50 55 5 146 4 49 4 97 0 3 0 7 6 53 6 145 1 47 1 98 1 3 1 7 5 52 7 143 9 44 8 99 1 3 2 7 5 12 6 15 21 7 178 1...

Page 22: ...4 6 20 6 3 10 4 8 138 5 31 00 169 5 15 2 26 4 6 2 150 4 31 9 182 2 16 1 26 9 6 9 162 2 32 8 195 0 16 9 27 4 20 13 2 180 1 33 71 213 8 18 2 28 1 15 2 190 9 34 7 225 6 18 8 28 5 16 2 201 7 35 7 237 4 19...

Page 23: ...Use 1 2 3 4 5 ON OFF FutureUse Acc 2 Dip 1 Acc 2 Dip 2 SeeFigure 1 for DHW wiring Current Transducer CT Thermistor Light emitting diode Green Relay coil Capacitor w bleed resistor Switch Condensate ov...

Page 24: ...EPPER ANA ACC2 DH DIV NO COM K6 NO COM K5 C R L1 L1 L2 L2 P12 P10 P5 P11 C R C R C R P4 P2 K1 K2 K3 HA2 HA1 SGI LOOP VS DATA VS PUMP PUMP SLAVE P3 V C R TX RX 5 P14 LLT P1 LAT FLOW LWT EWT CT2 4 3 CT2...

Page 25: ...agePCB traces Junction Quick connect terminal Wire nut Fieldwire lug Ground Fuse Legend Relay Contacts N O N C G T 1 3 2 P L1 Breaker CC Compressor Contactor FP1 Freeze Protection FP2 Freeze Protectio...

Page 26: ...door Unit Power Supply L1 L2 L3 L2 L1 L3 G Di sconnect fus ed disc onnect op onal F1 F2 F3 L1 L2 L3 L2 L1 L3 F7 F8 F9 Comp 1 Fuses Comp 2 Fuses Black G White H Red J Compressor A CCA T1 L1 T2 L2 T3 L...

Page 27: ...The latest version of this document is available at www waterfurnace com Contractor P O Engineer Project Name Unit Tag SD2552WNB 09 16 27 Page _____ of _____ ENVISION2 NKW REVERSIBLE CHILLER 50Hz Wiri...

Page 28: ...the factory using water Quality control system shall automatically perform via computer triple leak check pressure tests evacuate and accurately charge system perform detailed heating and cooling mod...

Page 29: ...trol Panel 1 Factory installed wired and functionally tested at factory before shipment 2 Single point power connection to non fused or fused rotary type disconnect in control panel 3 Factory installe...