36
INTELLIZONE2 SPECIFICATION CATALOG
SAH Blower Performance Data Option C
5 Series - Single Speed Split with SAH Air Handler
Split
Model
SAH
Model
Motor HP MAX ESP
Variable Speed ECM Settings with IntelliZone2 Blower Level Percentages
1
2
3
4
5
6
7
8
9
10
11
12
036
036
1/2
0.50
550
650
700
800
G
850
900
950
1050
L 55%
1100
70%-85%
1200
H 100%
1300
Aux
042
042
1
0.75
650
750
800
900
G
1000
1150
L 55%
1200
70%
1300
85%
1400
H 100%
1500
1600
1700
Aux
048
048
1
0.75
650
750
800
900
1000
G
1150
1200
1300
L 55%
1400
70%
1500
85%
1600
H 100%
1700
Aux
060
060
1
0.75
950
1100
G
1200
1350
1500
L 55%
1650
70%
1700
1800
85%
2000
H 100%
2100
Aux
2200
070
066
1
0.75
950
1100
G
1200
1350
1500
1650
L 55%
1700
70%
1800
2000
85%
2100
H 100%
2200
Aux
Blower level percentages are shown with factory recommended blower speed settings
L and H settings MUST be located within boldface CFM range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required for the auxiliary heat package
“G” may be located anywhere within the airflow table
CFM is controlled within 5% up to the maximum ESP
Max ESP includes allowance for wet coil and standard filter
SAH Air Handler with control option “C”
3/10/2017
5 Series - Dual Capacity Split with SAH Air Handler
Split
Model
SAH
Model
Motor HP MAX ESP
Variable Speed ECM Settings with IntelliZone2 Blower Level Percentages
1
2
3
4
5
6
7
8
9
10
11
12
026
026
1/2
0.50
400
G
500
600
L 55%
700
70%
800
85%
900
H 100%
1000
1100
1200
Aux
038
036
1/2
0.50
550
650
700
G
800
850
L 55%
900
950
70%
1050
85%
1100
1200
H 100%
1300
Aux
049
048
1
0.75
650
750
800
G
900
1000
L 55%
1150
1200
70%
1300
1400
85%
1500
1600
H 100%
1700
Aux
064
060
1
0.75
950
G
1100
L 55%
1200
1350
70%
1500
1650
1700
85%
1800
2000
H 100%
2100
Aux
2200
072
066
1
0.75
950
1100
G
1200
1350
L 55%
1500
1650
70%
1700
1800
85%
2000
2100
H 100%
2200
Aux
Blower level percentages are shown with factory recommended blower speed settings
L and H settings MUST be located within boldface CFM range
“Aux” is factory setting for auxiliary heat and must be equal to or above the “H” setting as well as at least the minimum required for the auxiliary heat package
“G” may be located anywhere within the airflow table
CFM is controlled within 5% up to the maximum ESP
Max ESP includes allowance for wet coil and standard filter
SAH Air Handler with control option “C”
3/10/2017