background image

10

FLUSHING OF SYSTEM:

To flush the system of any debris and air after installation is complete, please perform the following steps:

 

1 . Rotate bypass handles to the bypass mode 

(Fig. 2 on page 4)

  .

 

2 . Turn on inlet water and check for leaks in the newly installed plumbing .

 

3 . Fully open a cold water faucet, preferable at a laundry sink or bathtub without an aerator .

 

4 .  Wait two to three minutes or until water runs clear, then turn water off and follow start-up instructions .

 

Below is the name of each cycle as it appears on the screen with a description of the cycle position . The timing of each cycle will 

vary depending on the unit size as set from the factory .

  Name 

of 

Cycle   Description

 

 BACKWASH 

   BACKWASH

 

 

REGENERANT DRAW DOWN 

 

BRINE DRAW AND SLOW RINSE 

  RINSE 

    RAPID 

RINSE

  FILL 

    BRINE 

TANK 

FILL

1 .   With the softener in the bypass mode 

(Fig. 2 on page 4)

 and the control valve in normal operation where the

display shows either the time of day or the gallons remaining, manually add 8” of water to the regenerant tank .

        NOTE:

 If too much water is put into the brine tank during softener start up, it could result in a “salty water”

complaint after the first regeneration . During the first regeneration, the unit will draw out the initial volume of brine/

regenerant and refill it with the correct, preset amount .

2 .   With the softener in bypass mode, press and hold the 

REGEN

 button until the motor starts . Release button . The display will read 

“Pend 0” for about three seconds while the system transfers from one tank to another . After the transfer is complete, the valve will 

automatically advance to the “Backwash” position . Once the valve has stopped in this position, unplug the transformer so that the 

valve will not cycle to the next position . Open the inlet handle of the bypass valve very slightly, allowing water to fill the tank slowly 

in order to expel air from the tank .

CAUTION:

  If water flows too rapidly, there will be a loss of media to the drain.

3 .  When the water is flowing steadily to the drain, clear and without the presence of air, slowly open the inlet valve .

Restore power and momentarily press the 

REGEN

 button to advance the control to the “BRINE” position .

4 .  With the bypass now in diagnostic mode 

(Fig. 3 on page 4)

, check to verify that water is being drawn from regenerant tank 

with no air leaks or bubbles in the brine line . There should be a slow flow to the drain . Disconnect brine line from the safety float 

valve in the brine tank and check for a vacuum . After proper confirmation, reconnect brine line, making sure to tighten securely .

5 .  Momentarily press 

REGEN

 again until the display reads “RINSE .” There should be a rapid flow to the drain . Unplug transformer 

to keep the valve in the “RINSE” position . Allow to run until steady, clear and without air . While the unit is rinsing, load the 

brine tank with water softener salt 

(refer to Brine Tank Maintenance and Salt section)

 . Restore power .

6 .   Push 

REGEN

 again and the unit will advance to the “Brine Refill” position . Check to make sure the brine tank is refilling . 

The flow rate is usually  .5 gpm for all residential and light commercial applications .

7 . Push 

NEXT

 and the unit will return to normal operation .

8 .  Place unit into bypass mode again 

(see Fig. 2 on page 4)

 and press and hold the regen button to allow control valve

to transfer to the second tank . Follow steps 2-7 to now expel air from this tank .

9 .  When finished expelling air from second tank, return bypass handles to normal operating position 

(see Fig. 1 on page 4)

 .

The unit is now online and soft water is available for use .

10 . 

 CONDITIONING OF MEDIA 

 To flush any remaining debris and air from the system again:

1 . Fully open a cold water faucet, preferably at a laundry sink or bathtub without an aerator .

2 . Wait two to three minutes or until water runs clear, then turn water off .

3 . Turn on hot water and check for air, then turn water off after air is discharged .

11 .  

SANITIZING OF UNIT UPON INSTALLATION AND AFTER SERVICE:

   At this time, it is advised to sanitize the softener:

  1 .   Open brine tank and remove brine well cover . 

  2 .  Pour 1 oz . of household bleach into the softener brine well .

NOTE:

 Avoid pouring bleach directly onto the safety float components in the brine well .

  3 . Replace brine well cover .
  Unit sanitizing will be complete when the first cycle is run and the bleach is flushed from the softener .
12 . Check time of day . Start-up is now complete .

START-UP INSTRUCTIONS

Summary of Contents for Impression Plus IMP-1044TW

Page 1: ...Twin Water Softeners For Models IMP 844TW ASP1 1044TW IMP 1044TW ASP1 1054TW IMP 1054TW ASP1 1354TW IMP 1354TW ASP1 1465TW IMP 1465TW ASP1 1665TW IMP 1665TW IMPRC 1054TW ASP2 1044TW IMPRC 1354TW ASP2...

Page 2: ...rated properly Please study this manual carefully and understand the cautions and notes before installing This manual should be kept for future reference If you have any questions regarding your water...

Page 3: ...dels Read Normal Operating Displays Set Time of Day Read Power Loss Error Display Be sure system and installation are in compliance with all state and local laws and regulations For the homeowner plea...

Page 4: ...r flows through the control valve for normal operation of a water softener or filter During the regeneration cycle this position provides regeneration water to the unit while also providing untreated...

Page 5: ...a firm level surface 1 The distance between the drain and the water conditioner should be as short as possible see step 8 2 Since salt must be periodically added to the brine tank it should be locate...

Page 6: ...s could cause interior damage to the flow control Install a 1 2 I D flexible plastic tube to the Drain Line Assembly or discard the tubing nut and use the 3 4 NPT fitting for rigid pipe recommended If...

Page 7: ...tion however an overflow line connection will direct the overflow to the drain instead of spilling on the floor where it could cause considerable damage This fitting is an elbow on the side of the bri...

Page 8: ...ation initiation will be called for on that day even if a sufficient number of gallons were not used to call for a regeneration By default this regeneration will occur at 2 00 a m Set Day Override usi...

Page 9: ...ed time after a regeneration if there is no salt or if another error has occurred Turn the alarm OFF or ON using the or buttons Press NEXT NOTE This feature allows you to program the time in which the...

Page 10: ...ess the REGEN button to advance the control to the BRINE position 4 With the bypass now in diagnostic mode Fig 3 on page 4 check to verify that water is being drawn from regenerant tank with no air le...

Page 11: ...dby tank online so there is no disruption of treated water Once this transfer is complete the depleted tank will regenerate and return to standby mode ready to enter service upon depletion of capacity...

Page 12: ...ally indicates that the salt level in the brine tank is too low to operate properly If CHECK SALT appears there will usually be an audible alarm that sounds also if turned on alerting you to these con...

Page 13: ...Restricted stalled meter turbine C Remove meter and check for rotation or foreign material D Meter wire not installed securely into three pin connector D Verify meter cable wires are installed secure...

Page 14: ...G Check refill setting in programming Check refill flow control for restrictions or debris and clean or replace H Damaged seal stack assembly H Replace seal stack assembly I Control valve body type a...

Page 15: ...ston position or disconnect power supply from PC board for 5 seconds and then reconnect B PC board not properly snapped into drive bracket B Properly snap PC board into drive bracket and then Press NE...

Page 16: ...seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect Then reprogram valve to proper setting B MAV NHBP motor wire not conne...

Page 17: ...uzzer will activate and the screen will display the error A Check for low flow leak Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply...

Page 18: ...ews on each side that retain the transfer drive cap assemblies on both sides of the valve 8 Once the screws are removed from retaining the inlet side transfer valve cap and the outlet drive motor tran...

Page 19: ...re to be certain the meter cable doesn t get under the drive cap while tightening as it will result in damaging the cable 17 Position the large white drive gear with the A pointing toward the one o cl...

Page 20: ...cover 1 2 CV3107 1 Motor 1 3 CV3002A Drive bracket spring clip Includes 5 6 1 4 CV3554WS PC board for Sanitizer Plus 1 CV3813WP PC board for Impression Plus 1 5 CV3110 Drive gear 12 x 36 3 6 CV3109 Dr...

Page 21: ...embly 1 3 CV3135 O ring 228 1 4 CV3011 1 piston assembly downflow 1 CV3011 01 1 piston assembly upflow 1 5 CV3174 Regenerant piston 1 6 CV3541 Drive backplate 1 REPLACEMENT PARTS IN OUT HEAD FOR TANK...

Page 22: ...22 REPLACEMENT PARTS...

Page 23: ...1 18 CV3264 WS2H bypass reduction gear axle 3 19 CV3110 WS1 drive reducing gear 12 x 36 3 20 CV3262 01 WS1 5 2 ALT 2BY reduction gear cover assembly 1 21 CV3592 Screw 8 1 PHPN T 25 SS 3 22 CV4049 T1 c...

Page 24: ...1 CV3195 01 Refill port plug assembly 1 2 CH4615 Elbow locking clip 1 3 CV4144 3 8 Elbow Parker fitting 1 4 CV3163 O ring 019 1 Although no tools are necessary to assemble or disassemble the valve th...

Page 25: ...embly BLUE CV3010 1G G injector assembly YELLOW CV3010 1H H injector assembly GREEN CV3010 1I I injector assembly ORANGE CV3010 1J J injector assembly LIGHT BLUE CV3010 1K K injector assembly LIGHT GR...

Page 26: ...n 1 Strt No Sil 1 REPLACEMENT PARTS Water flow Proper DLFC orientation directs water flow towards the washer face with rounded edge DRAIN LINE ASSEMBLY 3 4 Item No Part No Description Qty 1 CH4615 Elb...

Page 27: ...1030 36S 4 x 36 slotted brine well 18 x 40 24 x 41 BT s 1 5 CH1018 2 piece overflow set 1 6 CH4500 48 474 air check assembly 1 2 x 48 1 7 CH4620 474 float assembly 7 1 8 CH4600 50 474 safety brine val...

Page 28: ...TANKS Item No Part No Description Qty CV4052 01 Interconnect kit for tanks 12 and larger 1 1 CV3151 Nut 1 QC 4 2 CV3150 Split ring 4 3 CV3105 O ring 215 4 4 CV3352 1 1 4 1 1 2 PVC solvent fitting 4 5...

Page 29: ...CV3105 O ring 215 2 4 CV3188 Fitting 2 3 4 BRASS SWEAT Item No Part No Description Qty CV3007 03 3 4 brass sweat assembly 2 1 CV3151 Nut 1 quick connect 2 2 CV3150 Split ring 2 3 CV3105 O ring 215 2...

Page 30: ...2 3 CV3105 O ring 215 2 4 CV3629 Fitting 2 3 4 BRASS SHARK BITE Item No Part No Description Qty CV3007 12 3 4 brass Shark Bite assembly 2 1 CV3151 Nut 1 quick connect 2 2 CV3150 Split ring 2 3 CV3105...

Page 31: ...31 This page left intentionally blank...

Page 32: ...26 0 25 0 26 0 25 0 Continuous Flow Rate GPM P PSI 9 0 2 4 9 0 2 8 9 0 2 7 19 0 15 0 19 0 15 0 Water Pressure Range PSI 25 100 25 100 25 100 25 100 25 100 Water Temp F 33 100 33 100 33 100 33 100 33...

Page 33: ...100 30 100 30 100 30 100 30 100 30 100 Water Temperature F 33 100 33 100 33 100 33 100 33 100 33 100 Electrical Requirements volts hertz 110 50 60 110 50 60 110 50 60 110 50 60 110 50 60 110 50 60 Pi...

Page 34: ...r replace the part or component at its expense and return part freight collect The above provisions of the warranty are valid as long as the unit is connected in compliance with local plumbing codes a...

Page 35: ...ess NEXT 4 Adjust minutes with and buttons 5 Press NEXT 6 Adjust current day with and buttons 7 Press NEXT to complete and return to normal operation DAYS TO A REGEN GPM 3 A FLOW RATE GPM 8 0 TIME OF...

Page 36: ...1900 Prospect Court Appleton WI 54914 Phone 920 739 9401 Fax 920 739 9406 2018 Water Right All rights reserved MAN WR TWIN RevA0818...

Reviews: