Pool Heat Pump
Temperature Calibration
It is possible to have a temperature variation between the water in the swimming pool and
the reading of the pool heat pump temperature probe (sensor). Example:if the water in the
pool is 26º C (80º F) and the heat pump electronic control displays 24ºC (76º F).
To calibrate this variation, perform the following procedure:
1. With the use of an accurate thermometer read the pool water temperature (e.g: 26˚C).
2. Read the temperature displayed on the pool heat pump electronic control (eg: 24˚C).
3. To determine the differential subtract the pool water temperature from the pool heat
pump displayed temperature, 26 - 24 = 2˚C. Therefore we must compensate for the 2˚C
variation.
4. Press
BOTH
the
UP
and
DOWN
arrow keys until the programmed temperature is
displayed ( the temperature you have previously set) then release both buttons.
5. Press the
ON/OFF
button and release.
6. Using the UP and DOWN arrows, enter the calibration value, (2˚C). In this case, by
pressing the UP arrow twice.
7. After 5 seconds when all the buttons have remained untouched , the display temperature
will show the pool water temperature as per your thermometer. If this is the case the
calibration process was successful.