I pg 18
Section 3. Installation
INDOOR VENTING — General Requirements
NOTE: REMOVE OR COVER “OUTDOOR ONLY” LABEL LOCATED ON HEATER OUTSIDE
PANEL WITH “INDOOR INSTALLATION” LABEL (P/N 474275) INCLUDED IN ACCESSORY
BAG (P/N 473607).
If installing the heater next to or near an air conditioning unit or a heat pump, allow a
minimum of 91.4 cm (36 in.) between the air conditioning unit and the heater.
!
CAUTION
Risk of fire and explosion.
Do not spray aerosols in the vicinity of the heater while it is in
operation. Chemicals should not be stored near the heater installation. Combustion air can
be contaminated by corrosive chemical fumes which can damage the heater and will void
the warranty.
!
WARNING
If you are considering connecting this heater to a pre-existing vent system, make sure that the
vent system meets the appropriate venting requirements as given in this manual on pages 17-
28. If not, replace the vent system. DO NOT use a draft hood with this heater. The Turbotemp
heaters are capable of a 270-degree discharge rotation and with a vent gas temperature less
than 204° C (400° F). The total length of the horizontal run must not exceed the length that is
listed in Table 7, Page 24.
INDOOR INSTALLATION
(SEE INSTALLATION GUIDE FOR CORRECT PLACEMENT OF THIS LABEL)
P/N 474275
Figure 11.