Note
(*) Combustion Air Intake Duct Connection Kit (Part Number 6844326) for all Turbotemp
heater models can be purchased separately. See page 52 for parts list.
DO NOT USE PVC PIPE FOR FLUE EXHAUST VENT. FLUE EXHAUST VENT
TEMPERATURES CAN BE IN EXCESS OF 400° F. FLUE EXHAUST VENT
MUST BE
CATEGORY I or CATEGORY III METAL VENT.
!
WARNING
Combustion 3 in. PVC Pipe
Inlet Air Intake Duct Requirements*
Combustion Air Intake 3 in. Pipe
(Vertical or Horizontal)
No. of 90° Elbows
Maximum Length in Feet (M)
0
70 ft. (21.3 M)
1
58 ft. (17.7 M)
2
46 ft. (14.0 M)
3
34 ft. (10.4 M)
4
22 ft. ( 6.7 M)