Section 3. Installation
1. All wiring must be in accordance with all
applicable codes and
must be wired by
a licensed electrician to AS3000 Wiring
rules.
2. The heater, when installed, must be
electrically grounded and bonded in
accordance with local codes or, in the
absence of local codes, with the National
Electrical Standards. A bonding lug is
provided on the outside of the panel
under the vent for this purpose.
3. Electrical power circuits to the pool heater
must follow local codes and National
Electrical Standards.
4. All wiring between the heater and devices
not attached to it, or between separate
devices which are installed in the field,
must be “Type T” wire rated for 35°C rise.
5.
The filter pump should run continuously
when the heater is on, and for at least 15
minutes after the heater turns off.
Any
switches in the pump circuit (including
circuit breakers) that can disconnect the
pump must also disconnect the heater.
6.
Do not wire single-pole switches,
including protective devices, into a
grounded line. The heater is not sensitive
to polarity.
Use the provided waterproof wire nuts when connecting the power supply.
A time clock controlling the filter pump should have a low-voltage Fireman’s Switch that
switches off the heater at least 15 minutes before shutting off the pump.
Please read the boxes headed “IMPORTANT! READ ME FIRST!” on pages 40 and 44 before
proceeding.
This heater is designed to operate at 240 VAC. It is not recommended to be connected
to OR operate on a 208 VAC.
!
CAUTION
CONNECTION OF FIREMAN’S SWITCH OR REMOTE CONTACT
AC Plug
240 Volt
Figure 22.