background image

Chimney, installed in accordance with the manufac-
turers  instructions  or  a  lined  masonry  chimney
acceptable to the authority having jurisdiction.

CHIMNEY CONNECTORS

THE CHIMNEY CONNECTOR is a smokepipe used
to connect the Leprechaun 90 O.S.A.  Stove to the
approved chimney described above.  The CHIMNEY
C O N N E C TOR  must  be  made  of  CORROSION
RESISTANT STEEL 24 gauge or heavier (“black” or
“blued”, or equivalent treated steel).

Be sure too fasten the chimney connectors together
and also to the flue outlet of the stove through the
holes provided.  Use at least two screws for each
joint.  Be sure the joints are tight and fully secured.

Chimney connectors shall not pass through an attic,
or roof space, closet or similar concealed space, or
a floor or ceiling.  Where passage through a wall, or
partition of combustible construction is desired, the
installation  shall  conform  to  CAN/CSA -B  365,
Installation code for Solid Fuel Burning Appliances
and Equipment.

Connectors should maintain a pitch or rise of at least
1/4” (6mm) to the foot from the stove to the chimney.
It should be installed so as to avoid sharp turns or
other construction features that would create exces-
sive resistance to the flow of flue gases.  It should be
securely supported with joints fastened with sheet-
metal screws, rivets, or other approved means.  The
entire length of a connector should be readily acces-
sible for inspection, cleaning and replacement.

The connector may pass through walls or partitions
constructed of combustible materials provided the
connector is either listed for wall pass-through or is
routed through a device listed for a wall pass-
through and is installed in accordance with the con-
ditions of the listing.

Any unexposed metal that is used as part of a wall
pass-through system and is exposed to flue gases
shall be constructed of stainless steel or other equiv-
alent material that will resist corrosion, softening or
cracking from flue gas at temperatures up to 982

o

C.

CONNECTING TO MASONRY CHIMNEY

The connector to a masonry chimney must extend
through the wall to the liner face or liner but not
beyond, and must be firmly cemented to masonry.

The connector may pass through walls or partitions
constructed of combustible material to a masonry
chimney provided the connector system selected is
installed in accordance with the proper clearances
and conditions  (See figures A,B,C,D page 8 & 9).

6

4.

All clearances shall be measured from the 
outer surface of the combustible material to 
the nearest point on the surface of the 
Leprechaun 90 O.S.A., disregarding any 
intervening protection applied to the com-
bustible material.

When using a manufactured wall shield system
observe local building codes and by-laws.

CHIMNEYS

Consult the LOCAL BUILDING CODE in all cases as
to the particular requirements concerning the 
installation  of  SOLID  FUEL

TYPE 

ROOM

HEATERS.  This Leprechaun 90 O.S.A. WOOD
BURNING STOVE is intended to be installed in
accordance 

with 

National 

Fire 

Protection

Associations  Standard  for  Chimneys,  Fireplaces
and Vents.  NFPA 211-1977.

The chimney must have a CROSS SECTIONAL
AREA of at least 193.5 sq. cm. (30 sq. inches).  It is
best connected to a chimney of the same size, as
connection to a larger size may result in somewhat
less draught.

The Leprechaun 90 O.S.A. is a Radiant Room
Heater and must be connected to a chimney of the
proper size and type, capable of providing an ade-
quate continuous draught of 0.06wg minimum.  It is
best to connect to a chimney of the same size as the
stove spigot.  DO NOT CONNECT TO A CHIMNEY
SERVING ANOTHER APPLIANCE
.

Minimum chimney height is 14’ 10” (4.5m) from floor
on which stove is installed.  An existing masonry 
chimney should be inspected, and if necessary,
repaired by a competent mason or relined, using an
approved relining system.  The stove must be 
connected to a chimney with a minimum continuous
draught of 0.06”wg. Poor draught conditions will
result in poor performance.

Note:   Connection to type “B” Gas Vents, approved
for connection to a certain gas burning appliance will
only result in a fire.

CHIMNEY TYPES - USA ONLY

The stove must be connected to a UL 103 Listed 
residential Type HT and Building Heating, Appliance
chimney installed in accordance with the manufac-
turers instructions or a masonry chimney 
constructed in accordance with NFPA 211 Chimney
vents and Solid Fuel Burning Appliances.

CHIMNEY TYPES -  CANADA ONLY

The stove must be connected to an Underwriters
Laboratories of Canada labelled Factory Built 650

o

C

Summary of Contents for LEPRECHAUN 90 O.S.A

Page 1: ...at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled If this stove is not properly installed a house fire may result For y...

Page 2: ...A REAR VENT REAR FLUE EXIT Fit back sealing plate Part no 17 over the top flue aperture in the hob Part no 13 Fit the flue spigot to part no 11 where part no 17 was making sure that part no 17 and par...

Page 3: ...1 4 6mm thick covered with 1 8 3mm sheet metal is required to cover the area under the heater and to extend to at least 18 450mm at the front and 8 200mm to the sides and rear This will provide pro t...

Page 4: ...ts between air vents and outside walls should be sealed to prevent ingress of mois ture l This stove is listed for Mobile home installa tion provided it is properly connected to an outside air supply...

Page 5: ...ances may be reduced by the percentage reduction as stated in the wall shield manufacturer s instructions For clearance reduction systems using an air space between the combustible wall and the wall p...

Page 6: ...ry The connector may pass through walls or partitions constructed of combustible material to a masonry chimney provided the connector system selected is installed in accordance with the proper clearan...

Page 7: ...nside Back Heat Shield 29 Door Sealing Rope 30 Outside Back Heat Shield 31 Spacers 32 Optional Pipe Shield 33 Heat Shield Blanking Plate 34 Tie Bolts 35 Top Baffle Plate Gasket 36 Back Panel Gasket 37...

Page 8: ...diameter as the chimney connector and having 1 25mm or more of insulation with a min 9 230mm air space between the outer wall of the chimney length and combustibles The inner end of the chimney lengt...

Page 9: ...less than 2 50mm from the face of the fireplace See Section under Minimum Clearances to Combustibles Before the installation the entire fireplace system should be inspected for condition and code com...

Page 10: ...your finger when the pipe is cool If you hear a dull echo the pipe may need cleaning Disassemble the chimney connector and clean the sections Replace corroded pipe sections The fit ting of a slip join...

Page 11: ...clean itself when there is sufficient heat generated by burning fuel The Air Way system provides pre heated warm air which keeps the glass clean WARNING DO NOT OPERATE THE STOVE WITH BROKEN GLASS 2 H...

Page 12: ...or hot embers or sparks from the chimney LEPRECHAUN 90 O S A MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS SIDE WALL TO STOVE 20 INCHES 510 mm BACK WALL TO CHIMNEY CONNECTOR 18 INCHES 460mm BACK WALL T...

Reviews: