8
PREMIER 2 SINGLE-SPEED INSTALLATION AND MAINTENANCE MANUAL
OPEN LOOP SYSTEMS
NOTE:
For open loop/groundwater systems or systems that do not contain an antifreeze
solution, set SW2-2 to the WELL position.
Typical open loop piping is shown below in Figure 9. Always maintain water pressure in
the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral
precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air
exposure. Ensure proper water flow through the unit by checking pressure drop across the heat
exchanger and comparing it to the figures in Table 2 on page 22. Normally, about 2 gpm flow rate
per ton of cooling capacity (1.5 gpm per ton minimum at 50
°
F) is needed in open loop systems.
Figure 9 -
Open System: Groundwater Application
Open Loop
Groundwater
Systems
Figure 8-
Premier 2 Slave Hook-up
Two Premier 2 units
One Premier 2 unit and one
Premier AT or Spectra unit
(with optional circut board)
SL1
In
SL1
Out
Not
Used
Not
Used
Shut
Down
C
C
Premier 2 Unit #1
With pump
wired to
Unit 1
With pump
wired to
Unit 2
SL1
In
SL1
Out
Not
Used
Not
Used
Shut
Down
C
C
Premier 2 Unit #2
SL1
In
SL1
Out
Not
Used
Not
Used
Shut
Down
C
C
Premier 2 Unit #1
With pump
wired to Unit 1
With pump
wired to
Unit 2
Not
Used
G L1
SLG SL
Premier or Spectra Unit #2
Normally Open
Contacts
1 2 3 4 5 6 7 8
24v
Coil
SX unit
C
SL1 IN
Premier 2 Unit Low Voltage
Wiring Legend
Low Voltage
High Voltage
FC 1 or FC 2
Flow Center
240v
pump
Premier
High
Voltage
PB1
L 1
L 2
Not
Used
One Premier 2 unit
and one Spectra
electro-mechanical unit
Boiler Drains
For HX Flushing
Solenoid Valve
Shut-Off
Valves
Rubber Bladder
Expansion Tank
Water Out
Water In
Flexible Duct Collar
Vibration Absorbing Pad
Low Voltage
to Thermostat and
Valve
Drain
Desuperheater
Connections
Auxiliary
Heater
Knockout
Disconnects
(If Applicable)
Flow Control
Valve
(on oulet of
solenoid
valve)
Unit Power
Auxiliary Heat Supply
Unit Supply
Strainer
P/T Plugs
Shut-Off Valve
(to isolate solenoid
valve while acid
flushing)