25
SYNERGY3D INSTALLATION MANUAL
Operating Limits
Heating
Cooling
Hot Water
Mode
STG1
STG2
STG3
eMeRG
STG1
STG2
Compressor
On
On
On
Off
On
On
Stg 2 On
Reversing Valve
Off
Off
Off
Off
On
On
Off
Loop Pump
On
On
On
Off
On
On
On
Load Pump
Off
Off
Off
Off
Off
Off
On
Aux Heater
Off
Off
Staged
Staged
Off
Off
Off
Acc Relay
On
On
On
Off
On
On
Off
Diverting Valve
Off
Off
Off
Off
Off
Off
On
ECM Speed
On
On
On
On
On
On
Off
T-Stat Signal
Y1
Y1, Y2
Y1, Y2, W
W
Y1, O
Y1, Y2, O
HW
Damper
Off
Off
Off
On
Off
Off
Off
Auxiliary 1 - Out
On
On
On
Off
On
On
On
Operation Logic
Operating Limits
Cooling
Heating
°F
°C
°F
°C
Air Limits
Minimum Ambient Air
45
7.2
45
7.2
Rated Ambient Air
80
26.7
70
21.1
Max. Ambient Air
100
37.8
85
29.4
Minimum Entering Air
50
10.0
40
4.4
Rated Entering Air db/wb
80.6/66.2
27/19
68
20.0
Maximum Entering Air db/wb
110/83
43/28.3
80
26.7
Water Limits
Minimum Entering Water
30
-1.1
20
-6.7
Normal Entering Water
50-110
10-43.3
30-70
-1.1
Maximum Entering Water
120
48.9
90
32.2
NOTeS:
Minimum/maximum limits are only for start-up conditions, and are meant for bringing
the space up to occupancy temperature. Units are not designed to operate at the minimum/
maximum conditions on a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When
any of the factors are at the minimum or maximum levels, the other two factors must be at the
normal level for proper and reliable unit operation.
All manuals and user guides at all-guides.com
Summary of Contents for Synergy3D
Page 2: ...All manuals and user guides at all guides com ...
Page 37: ...37 SYNERGY3D INSTALLATION MANUAL Notes All manuals and user guides at all guides com ...
Page 38: ...38 SYNERGY3D INSTALLATION MANUAL Notes All manuals and user guides at all guides com ...
Page 39: ...All manuals and user guides at all guides com ...