background image

6

INSTRUCTION GUIDE: ElITE COmmUNICaTING ThERmOSTaT

IG1602EW    06/12

Both

 – hUmIDIFY operates in the hEaT mode and 

DEhUmIDIFY operates in COOl mode.

None

 – Neither is active.

Reversing Valve Option

Option of the reversing valve (O output) being on when in 
cooling or heating. Default is COOlING.

Restore Defaults

This will allow you to revert to the factory default settings. 

Anticipator

This adjustment controls the sensitivity and cycle rate of the 
thermostat. higher numbers decrease the cycle rate. lower 
numbers increase the cycle rate. Default value is 0, and the 
range is 0-4. 

Differential

This adjustment will vary the number of degrees, from the set 
point, before a call for heating or cooling is made. adjustments 
can range between 0.5˚ and 4˚ differential. Default is 0.5˚ offset. 
(If your set point is 70˚F in heating, your thermostat will not call 
for heat until the temperature is 69.5˚F, with a 0.5 differential).

Cycles Per Hour

This feature will not allow more than the specified number of 
equipment cycles per hour. Values can range from 4 or 6 (or 1 
cycle every 15 minutes (default) or 1 cycle every 10 minutes, if 
6 is set). Factory default setting is 4. This default selection will 
provide optimum performance in nearly all installations.
MENU → SETTINGS → CYCLES PER HOUR

Program Settings

MENU → SETTINGS → PROGRAM SETTINGS

Smart Recovery

Smart recovery is a feature of your thermostat designed to 
improve comfort by adjusting temperatures to achieve a room 
temperature by the programmed time. When it’s time for a 
programmed temperature change, smart recovery begins working 
in advance, turning the system on and off as needed to adjust 
the indoor temperature. During these transition periods, you 
may notice that the actual temperature and your temperature 
setting don’t match. That’s smart recovery in action, adjusting 
temperatures in small increments for greater energy efficiency. 
This is more energy efficient than simply allowing the system to 
operate at full capacity until the desired temperature has been 
met. Smart Recovery helps avoid excessive use of auxiliary heat 
when recovering from night setback in the heating mode. 

To cancel the message, select the CaNCEl alaRm, and press 
the center button ■.

Input Dealer Info

Contractors are able to input Contractor Name, and Contractor 
Phone number into these screens. The model and serial number 
are communicated from the unit. This way, the owner could give 
this information to the contractor so that he would know what 
system the owner has prior to the service visit.              

1.  Scroll to the info you want to enter and press the center 

button ■.

2.  Enter the information by scrolling through the characters 

using the up & down arrows ▲▼. Once the character you 
want is set, press the right arrow ► to move to the next 
space and begin entering another character. 

3.  Once you’ve completed filling out the field, press the center 

button ■ to save the entry and return to the INPUT DEALER 
INFO screen. Repeat this process for all fields you want 
saved. 

4.  Once all fields have been entered, scroll to SaVE and press 

the center button ■.

Fan with Heat Option

Options are ON or OFF. This selection determines whether G 
(fan) output is to be ON or OFF when W (auxiliary heat) output 
is ON. 

Humidity Option (TPCM32U04 Only)

If your system is setup with a humidifier, or you desire a 
dehumidification option, select the appropriate setting. 

hUmIDIFY (TPCm32U04 only)
DEhUmIDIFY (TPCm32U04 only) 
BOTh  (h or Dh)   
NONE

To adjust the Set Point for humidification or Dehumidification, 
Select the Rh from the main menu. The values can be selected 
and adjusted from that screen.

NOTE:

 If you have an outdoor sensor attached to the 

thermostat, the humidification setting is adjusted automatically 
based on the outdoor temperature.

Humidify

 – Turns on the h output when the room humidity is 

below the set point and mODE is set to hEaT, EhEaT, 
or aUTO when heating was the last mode run.

Dehumidify

 – Turns on the Dh output when the room humidity is 

above the set point and the mODE is set to COOl or 
aUTO when Cool was the last mode run.

Summary of Contents for TPCM32U03

Page 1: ...to save the hour 8 SET MINUTE by using the up and down arrows and then press the center button on the keypad to save the minute 9 Date and Time are now set You can return to the Main Menu by pressing...

Page 2: ...u scroll to MENU and press the center button on the keypad 2 Select SETINGS SCREEN SETTINGS BACKLIGHT ON TIME 3 You can change the backlight on time by using the up and down arrows 30 60 90 120 and ON...

Page 3: ...mostat automatically switches itself from heating to cooling or vise versa based on the setpoints When setting up the thermostat you have to enter both a cooling setpoint and a heating setpoint The th...

Page 4: ...all back into the wall c As each wire is disconnected record wire color and terminal marking d Discard or recycle old thermostat NOTE Mercury is a hazardous waste and MUST be disposed of properly 3 Se...

Page 5: ...crements or Calendar Time can be set to OFF or 3 48 months in 3 month increments Humidifier Cumulative Run Time default is 0 hours OFF and Calendar Time is OFF Values can range from 400 3600 hours for...

Page 6: ...n simply allowing the system to operate at full capacity until the desired temperature has been met Smart Recovery helps avoid excessive use of auxiliary heat when recovering from night setback in the...

Page 7: ...heating and cooling setpoint For instance if you are away from your home from 8am to 5pm make this period of time an event and set the thermostat at an energy saving setting You have the option of set...

Page 8: ...IG1602EW 06 12 2012 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product research and development and reserves the right to cha...

Reviews: