background image

20

TRUCLIMATE 700 90-140 TON  INSTALLATION MANUAL 

Water Quality

1.0. Minimum Fluid Volume

A.  Water-to-water heat pumps require a minimum amount 

of source and load side fl uid volume to ensure accurate 
and stable temperatures during system operation. 
For normal air conditioning type applications, it is 
recommended to use at least 7 gallons/ton. 

B.  Applications that require more precise temperature 

control or low loading will occur the minimum 
fl uid volume shall be no less than 10 gallons/ton. 
Installation of a buff er tank that will properly mix the 
fl uid is recommended. 

1.1. Water-to-Water Heat Pump Sizing

A.  Heat pumps should be adequately sized for optimal 

system effi

  ciency and run time. Oversizing by more 

than 15% can diminish performance resulting in higher 
power consumption, short cycling of compressors, and 
unstable conditioning temperatures.

B.  In applications where the minimum load is signifi cantly 

less than the design condition, it is better to install 2 
smaller heat pumps for load matching rather than a 
single large heat pump.

1.2. Heat Pump Piping

A.  Multiple heat pumps can be installed in series or 

parallel confi gurations. The preferred system design is 
to pipe the equipment in parallel due to its simplicity 
and fl exibility. In parallel systems, the heat pump 
equipment can vary in size as long as fl ow rate and 
system volume are accounted for. 

B.  Piping equipment in series is not desired; however, 

it can be done if proper guidelines are followed. 
Always observe proper temperature and fl ow rate 
requirements for each unit. Sometimes this method is 
desired to achieve larger temperature diff erences. 

1.3. Strainers

A.  All brazed-plate heat exchangers shall have a 

strainer within 8 ft of the water/brine inlet. It is highly 
recommended to use a minimum of 60 mesh in order 
to provide maximum fi ltration. In any case, the strainers 
should never have a mesh size less than 20.

B.  Failure to install proper stainers and perform regular 

service can result in serious damage to the unit, and 
cause degraded performance, reduced operating life 
and failed compressors. Improper installation of the 
unit (which includes not having proper strainers to 
protect the heat exchangers) can also result in voiding 
the warranty. 

C.  Strainers should be selected on the basis of acceptable 

pressure drop, and not on pipe diameter. The strainers 
selected should have a pressure drop at the nominal 
fl ow rate of the units; low enough to be within the 
pumping capacity of the pump being used.

1.4. Flow Sensing Devices

A. A 

fl ow switch or equivalent must be installed on the 

evaporator for each unit to be installed. If the unit is to 
operate as both modes (heating/cooling), a fl ow switch 
is needed on both heat exchangers. 

B. A 

diff erential pressure switch can be used in place of a 

fl ow switch. The diff erential switch must be capable of 
pressure range as indicated in the pressure drop tables.

1.5. Water Quality

A. 

General:

 Reversible chiller systems may be successfully 

applied in a wide range of commercial and industrial 
applications. It is the responsibility of the system 
designer and installing contractor to ensure that 
acceptable water quality is present and that all 
applicable codes have been met in these installations.

B. 

Water Treatment: 

Do not use untreated or improperly 

treated water. Equipment damage may occur. The 
use of improperly treated or untreated water in this 
equipment may result in scaling, erosion, corrosion, 
algae or slime. The services of a qualifi ed water 
treatment specialist should be engaged to determine 
what treatment, if any, is required. The product 
warranty specifi cally excludes liability for corrosion, 
erosion or deterioration of equipment.

 

The heat exchangers in the units are 316 stainless steel 
plates with copper brazing. The water piping in the 
heat exchanger is steel. There may be other materials 
in the building’s piping system that the designer may 
need to take into consideration when deciding the 
parameters of the water quality.

 

If an antifreeze or water treatment solution is to be 
used, the designer should confi rm it does not have a 
detrimental eff ect on the materials in the system.

C. 

Contaminated Water:

 In applications where the 

water quality cannot be held to prescribed limits, the 
use of a secondary or intermediate heat exchanger 
is recommended to separate the unit from the 
contaminated water.

 

The following table outlines the water quality 
guidelines for unit heat exchangers. If these conditions 
are exceeded, a secondary heat exchanger is required. 
Failure to supply a secondary heat exchanger where 
needed will result in a warranty exclusion for primary 
heat exchanger corrosion or failure.

 

WARNING: Must have intermediate heat exchanger 
when used in pool applications.

Summary of Contents for TruClimate 700

Page 1: ...entive Maintenance TruClimate 700 90 140 Ton Installation Manual I ll i M l Commercial 60 Hz Water Cooled Chiller R 513A Refrigerant 90 140 Ton Lead Variable Speed Compressor Installation Information...

Page 2: ......

Page 3: ...stance Transport 19 Water Quality 20 Water Connections 22 Operating Limits 22 Electrical Data 23 Electrical Connections 23 Electrical System and Controls Safety Circuit 24 Wiring Schematics 26 HydroLi...

Page 4: ...condition Examine units for shipping damage removing unit packaging if necessary to properly inspect unit Units in question should also be internally inspected If any damage is observed the carrier s...

Page 5: ...oltage 4 460 60 3 Electrical Option A Fused Disconnect Control Option D Primary Unit Master Controller Non Standard Options SSS None Future Option N Not Applicable Future Option 0 Not Applicable Futur...

Page 6: ...modules B 3 modules C 4 modules D 5 modules Family HSC HydroLink Supervisory Control Chiller Module N NXW Compact Scroll D WC Dual Scroll Modular Chiller S WCHVE VS Dual Screw Chiller Header Rack A No...

Page 7: ...d standard provisions for remote access using BACnet Color touch screen chiller interface provides easy to use instant access to unit performance Low impedance line reactors reduce harmonic noise and...

Page 8: ...speed drive integrated with compressor provides envelope control for improved reliability DC Inverted Variable Speed Single Screw Compressor Removable 4 pipe header rack Full enclosure foam lined pan...

Page 9: ...d WaterFurnace modular screw units feature several industry firsts to provide a true modular chiller 1 Modular chiller unit can be removed from the bank and replaced with a new unit using strategicall...

Page 10: ...10 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data...

Page 11: ...11 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Service Clearance...

Page 12: ...12 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Center of Gravity...

Page 13: ...13 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Rigging Data...

Page 14: ...er in the back It is recommended to carry the load a low as possible maximum of 2 inches NOTE The placement of the compressor and heat exchangers on this unit creates greater weight toward the rear 4...

Page 15: ...INSTALLATION MANUAL Chiller Installation cont 5 Remove 4 u bolts image below and retain for later installation 6 Remove 4 pipes that are attached to the pipe rack in shipment image below Remove 4 U bo...

Page 16: ...victaulic connections that were previously removed 8 Using a forklift move main unit into position carefully guiding pipes from heat exchangers into the pipe rack 9 Once both unit and pipe rack are in...

Page 17: ...TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Chiller Installation cont 10 Install bolts along the junction of pipe rack frame and unit body 11 Attach the quick connect isolation valves and flow switc...

Page 18: ...e unit frame see image 2 Slightly lift 2in maximum the module and pull away from the bank Make sure the module sensors do not come into contact with any of the structural members of the header rack 3...

Page 19: ...sport 1 When lifting the chiller all lifting brackets must be used 2 Always use spreader bars The sound enclosure of the chiller may be damaged if spreader bars are not used 3 The front pockets of the...

Page 20: ...the basis of acceptable pressure drop and not on pipe diameter The strainers selected should have a pressure drop at the nominal ow rate of the units low enough to be within the pumping capacity of th...

Page 21: ...en egg smell appears at 0 5 ppm 10 50 ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Chlorides Less t...

Page 22: ...art up is scheduled Each water header is equipped standard with a temperature well sensor for supply and return water temperatures of the units performance Also included is a flow switch located on th...

Page 23: ...A Min Circ Amp Max Fuse HACR MOA RLA LRA1 090 460 60 3 414 506 190 0 156 0 20 0 156 0 195 0 350 115 460 60 3 414 506 225 0 185 0 20 0 185 0 231 3 400 140 460 60 3 414 506 290 0 240 0 20 0 240 0 300 0...

Page 24: ...he compressor contactor CC output of the Aurora control Anytime Aurora senses a fault that would require compressor shutdown it will trigger the STO input to turn the motor off High Pressure Switch NC...

Page 25: ...25 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Wiring Schematic next page...

Page 26: ...NET P6 RS485 EXP P3 SW2 On Future Use L Output Type CC Dual Single Acc Dip 5 Acc Dip 4 RV B O FP2 15 F 30 F FP1 15 F 30 F Com1 LED5 Com2 LED5 Test Mode F1 3A P1 C PWM 1 2 3 4 5 6 7 8 ALM ALG ACC COM A...

Page 27: ...ED PRESSURE TRANSDUCER T TEMP SENSOR LPS LOW PRESSURE SWITCH HPS HIGH PRESSURE SWITCH Hydrolink 2 Controller 24VAC DC RS 485 1 S EEV HR4 4 3 2 1 Red White Green White SA5 Black SA4 Yellow SA3 Red SA2...

Page 28: ...splayed on the factory mounted touchscreen tablet Each chiller is equipped with a hardwire Ethernet connection that offers additional connectivity options to display chiller information without tappin...

Page 29: ...nnected to ALG Access Relay Operation SW2 4 SW2 5 Cycles with Blower ON ON Cycle with Compressor OFF OFF Water Valve Slow Opening ON OFF Reserved OFF ON Software Features Safety Features The following...

Page 30: ...ec recognition of the EST Condenser or Evaporator HX temperature above specified limit It is recommended that the Alarms be set 1 2 degrees off of the Fault set points so that the Alarm will trigger f...

Page 31: ...e Flash Code 4 Load Shed Flash Code 5 ESD Flash Code 6 Future Use Flash Code 7 Future Use Configuration LED LED2 Yellow Description of Operation Configuration LED Yellow Not used Fast Flash Fault LED...

Page 32: ...ime power measurement Watt of compressor Performance Monitoring provides entering and leaving loop water temperatures loop flow rate as well as heat of extraction or rejection rate into the loop requi...

Page 33: ...r Soft Open Crkt Run Start or welded cont 11 Not Used 11 Yes Hard or Soft Not used ABC AXB Advanced Faults 12 Not Used 12 Not Used 13 Non CriticAXBSnsrErr 13 No Auto Any Other Sensor Err 14 CriticAXBS...

Page 34: ...opens for 5 continuous seconds the compressor s will be immediately shut down until flow returns If flow does not return within 60 seconds the controller will issue an E 31 fault code for Source Flow...

Page 35: ...ngle shielded twisted pair cable 22 gauge to the RS 485 card on the HydroLink Aurora on one of the chillers Daisy chain to each additional chiller BACnet The BAS will land a single shielded twisted pa...

Page 36: ...36 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Evaporator Pressure Drop...

Page 37: ...37 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Condenser Pressure Drop...

Page 38: ...e has been Running for 4 Minutes Suction Temperature Discharge Pressure Super Heat Hx1 Gas Pressure Subcooling Hx1 Sat Capacity Hx2 Gas Pressure Return Water from Geo Field Hx2 Sat Hx2 Gas Temperature...

Page 39: ...39 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...

Page 40: ...quare inch HC Heating Capacity in MBTUH HE Heat of Extraction in MBTUH kW kilowatt ft hd pressure drop in feet of head HR Heat of Rejection Verify the following High voltage is correct and matches nam...

Page 41: ...is Check water flow rates and pressure drops across evaporators and condensers Verify graphical data and trending Properly document all data Annual Checks Remove and clean all waterside strainers Back...

Page 42: ...tal Amps Comp Fan n _____ AMPS n ______ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o...

Page 43: ...VERIFY ALL REFRIGERANT VALVES ARE OPEN OK NG VERIFY ELECTRICAL PANELS ARE FREE OF FOREIGN MATERIALS AND ALL WIRING IS TIGHT AND SECURE OK NG L1 L2 VOLTAGE V L1 L3 VOLTAGE V L2 L3 VOLTAGE V L1 TO GROUN...

Page 44: ...LOAD SIDE ANTIFREEZE CONCENTRATION TYPE CONDENSER LOAD SIDE ANTIFREEZE CONCENTRATION TYPE SOURCE LOAD SIDE ANTIFREEZE CONCENTRATION TYPE APPROVAL OF ANTIFREEZE CONCENTRATION TO ADJUST FREEZE PROTECTI...

Page 45: ...ED CONTROLS ONLY OK NG VERIFY WATER TEMPERATURES CLOSELY MATCH REFRIGERANT SAT TEMPERATURES OK NG VERIFY COMPRESSOR AND UNIT SETTINGS ARE CORRECT SEE SHEET BELOW OK NG COMPUTER STATIC IP ADDRESS IF AP...

Page 46: ...L LEVEL OK NG MODE F ENTERING HOT WATER TEMP F LEAVING HOT WATER TEMP F ENTERING COLD WATER TEMP F LEAVING COLD WATER TEMP F COMPRESSOR 1 CAPACITY COMPRESSOR AMPERAGE A COMPRESSOR 2 CAPACITY COMPRESSO...

Page 47: ...47 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Pages Description Date By All Document Creation 13 April 2023 MA Revision Guide...

Page 48: ...research and development and reserves the right to change design and speci cations without notice Product TruClimate 700 Type Water Cooled Chiller 60 Hz Size 90 140 Tons Document Installation Manual I...

Reviews: