29
TRUCLIMATE 700 90-140 TON INSTALLATION MANUAL
HydroLink2 Aurora Chiller Controls cont.
Field Selectable Options via Hardware
DIP Switch (SW1) – Test/Configuration Button (See SW1
Operation Table)
Test Mode
The control is placed in the test mode by holding the push
button switch SW1 for 2 - 5 seconds. In test mode most of
the control timings will be shortened by a factor of sixteen
(16). LED3 (green) will flash at 1 second on and 1 second off.
Additionally, when entering test mode LED1 (red) will flash
the last lockout one time. Test mode will automatically time
out after 30 minutes. Test mode can be exited by press-
ing and holding the SW1 button for 2 to 5 seconds or by
cycling the power. NOTE: Test mode will automatically be
exited after 30 minutes.
Reset Configuration Mode
The control is placed in reset configuration mode by holding
the push button switch SW1 for 50 to 60 seconds. This will
reset all configuration settings and the EEPROM back to
the factory default settings. LED3 (green) will turn off when
entering reset configuration mode. Once LED3 (green) turns
off, release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 FP1 Selection – Low water coil temperature limit setting
for freeze detection. On = 30°F [-1.1 °C]; Off = 15°F [-9.4°C].
On is default.
SW2-2 FP2 Selection – On = 30°F [-1.1 °C]; Off = N/A. On is
default.
SW2-3 RV – O/B - Reversing Valve Position. Normally cooling
"B" or normally heating "O" On = O; Off = B. B is default.
SW2-4 and 2-5 Access Relay Operation (P2). On and On is
default.
SW2-6 CC Operation – selection of single or dual capacity
compressor. On = Single Stage; Off = Dual Capacity. On is
default.
SW2-7 Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and ALM
Outputs. On = Continuous; Off = Pulsed. On is default.
SW2-8 Future Use. On is default.
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By
cutting JW2, ALM becomes a dry contact connected to ALG.
Access Relay Operation
SW2-4
SW2-5
Cycles with Blower
ON
ON
Cycle with Compressor
OFF
OFF
Water Valve Slow Opening
ON
OFF
(Reserved)
OFF
ON
Software Features
Safety Features
The following safety features are provided to protect the
compressor, heat exchangers, wiring and other components
from damage caused by operation outside of design
conditions.
Fuse –
a 3 amp automotive type plug-in fuse and each ABC
provides protection against a low Voltage short circuit or
overload conditions.
Anti-Short Cycle Protection –
5 minute anti-short cycle
protection for the compressor.
Compressor Minimum On Time -
5 minute minimum on-time
protection for the compressor to insure oil circulation for each
compressor cycle.
Random Start –
5 to 80 second random start upon power up
and return from load shed or emergency shutdown.
Fault Retry –
in the fault condition, the control will stage off
the outputs and then “try again” to satisfy the Y input call.
Once the thermostat input calls are satisfied, the control will
continue on as if no fault occurred. If 3 consecutive faults
occur without satisfying the thermostat Y input call, then the
control will go to lockout mode.
Lockout –
when locked out, the Alarm output (ALM)
and Lockout output (L) will be turned on. The fault type
identification display LED1 (Red) shall flash the fault code.
Lockout may also be reset by turning power off for at least 30
seconds or through HMI or BACnet.
High Pressure –
The E2 fault is recognized when the Normally
Closed High Pressure Switch, P4-9/10 opens, no matter how
momentarily. The High Pressure Switch is electrically in series
with the Compressor Contactor and serves as a hardwired
limit switch if an overpressure condition should occur.
Low Pressure -
The E3 fault is recognized when the Normally
Closed Low Pressure Switch, P4-7/8 is continuously open for
30 seconds. Closure of the LPS any time during the 30 second
recognition time restarts the 30 second continuous open
requirement.
Loss of Charge -
the E6 fault is recognized when the Normally
Closed Low Pressure Switch, P4-7/8 is open prior to the
compressor starting.
Summary of Contents for TruClimate 700
Page 2: ......
Page 10: ...10 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data...
Page 11: ...11 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Service Clearance...
Page 12: ...12 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Center of Gravity...
Page 13: ...13 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Rigging Data...
Page 25: ...25 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Wiring Schematic next page...
Page 36: ...36 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Evaporator Pressure Drop...
Page 37: ...37 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Condenser Pressure Drop...
Page 39: ...39 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...