9.3
Refrigerant charge and additional charge – EcoTouch Ai1 Air (Zubadan)
The outdoor units come fully charged with refrigerant R410A from the facto-
ry, allowing tube lengths (one way) up to 30 m without requiring additional
charging.
If tube lengths are less than 30 m, the charge in the outdoor unit is suffi-
cient. In new units, excess refrigerant must not be drained. However, to op-
timise the unit we recommend individual adjustment of refrigerant quantity
to total volume (refer to table).
Heat pump
Factory
pre-
charge
[kg]
Total charge at
line length (one way) [kg]
11-20m
21-30 m
31-40 m
41-50 m
51-60 m
61-75 m
>75m
Zubadan
5,5
-0,4
-0,2
+0,6
+1,2
+1,8
+2,4
not
possible
If line length exceeds 30 m, charge unit with additional R410A refrigerant.
Please note: Do not exceed permissible line length LMAX (75 m)!
Outdoor unit
Between indoor and outdoor unit
Outer diameter of
connection-
lines
Max. height dif-
ference H [m]
Max. line length
L [m]
Max. number of
elbows
Zubadan
30 m
75 m
15
Liquid: Ø 10.0
Gas: Ø 16.0