WL270

 Manual 

                                                                    Page 52 – Revision 3‐4‐2019 

Thermostat or overload 
“open” on Hot Tank 

Turn Power off.  Check OHM’s resistance across terminals on 
each Thermostat and Overload separately. 
 
Good components will indicate a closed circuit or zero 
OHM’s on the meter. 
 
Replace components as necessary. 

Loose or improperly 
connected wire(s) to the 
heating element / hot tank. 

Visually inspect wire leads gong to the hot tank; confirm 
proper connections to the heating elements. 
 
 Hot tank life is 3‐5 years, depending on usage.   
 

*Typically, dealers swap out the hot tank at site, take back to 
the shop to repair. 

Heating Coil not Working 

Turn Power off; Drain hot tank; Use multi‐meter to check 
heater element for approximately 26 OHM’s resistance. 
 
Hot tank must be empty if you are checking for continuity.   
 
Replace Hot Tank as necessary. 

 

 
 

 