PUMP OVERHAUL
Page 10 of 21
E511-C Gear Case Cover and Impeller Shaft Removal
1.
Remove the 10 hex head screws and lock
washers from the gear case cover.
2.
Remove the gear case cover from the gear
case. Press out the impeller shaft and bear-
ing assembly from the gear case cover.
3.
Remove gear case gasket.
4.
Press out the mechanical seal stationary seal
ring, oil seal. Pull wear ring if required.
Oil Seal
Stationary Ring
O-ring
Impeller Shaft and Bearing Assembly
Gear Case Gasket
Gear Case Cover
Wear Ring
Lock Washer, 3/8 in.