background image

4211-1661   01/28/2022

APPENDIX: SYSTEM INSTALLATION

APPENDIX: SYSTEM INSTALLATION

page 5           

DIAGRAM 8:  LOCATING THE STEAM HEADS

12” MIN 

(305 mm)

18” MIN 

(46 mm)

12” MIN 

(305 mm)

18” MIN 

(46 mm)

6” MIN

(150 mm)

12” MIN 

(305 mm)

12” MIN 

(305 mm)

IMPORTANT

The steam pipe entry into the steam

room and the steam head must be

caulked to avoid damage caused

by steam leakage into the wall.

Centering the steam pipe is critical 

through walls made of plastic, 

acrylic, resin, fiberglass, or similar

 

materials. Allowing the pipe to touch

materials not rated for 212°F (100°C) 

or higher will result in damage 

to these materials.

If the steam line is in an area where the

temperature will be below 40°F (4°C) or 

if the line is more than 20 feet (6 m) long,

insulate the steam line for best results.

 

SECTION  5:  WIRING INSTRUCTIONS

1. 

ELECTRICAL ROUGH-IN

Use correct size and type of power wires and circuit breakers to meet electrical codes. Leave 4 feet (1,2 m) of slack wire at generator location to finish hookup. 

Connect each generator to a dedicated circuit breaker. 

ELECTRICAL FINISH

At the generator, route the copper supply wire with an appropriate strain relief through the hole marked POWER ENTRY. Connect the supply wires to the power 

terminal block. Refer to the wiring diagrams to determine your connection points and the necessary jumper connection. Connections can be varied to use either 

single phase or 3 phase or 3 phase +Neutral. Connect the earth ground to the ground lug (green screw). 

Notes

•  Two power circuits are required for 208V WWSU11 and for 208 and 240V WWSU15.

 

•  Supply voltage must be 200V or higher. 240V models may be used with available voltages to 240V (and 380V-415V~3N).

•  Use copper power wire only! All wire is to be UL Listed, 300V 75°C minimum unless otherwise specified.

 

•  

A GFI device is not required by UL or NEC. One may be installed if required by local codes or the owner.  

   A GFI device will tend to nuisance trip due to heater element aging.

          

3. 

CONNECT STEAMERS TOGETHER

 

Connect a control cable from the Primary steamer’s G1 or G2 jack to the secondary steamer’s AK IN jack. Repeat for the third steamer, if installed.  Note: We 

recommend system steamers be of similar wattages and, if not the same, the largest wattage should be in the primary steamer. 

See diagram below.

1

4

5

8

100mA TIME DELAY

3224-

1A NON-TIME DELAY

+

SVC

+

+

WATER

S60 B

S60 A

S30A

G2

AK I

N

60m/24HR

NORM/EXT

F/ C

12

3

OO

DRAIN

W-D COM

S30B

G1

2403-23  REV. B

C

SAUNATEC 2016

K1

K6

K3

K4

K5

K2

J15

K8

K7

F2

F1

VR1

C20

C19

C21

BR1

J1

8J

17

J1

9

L

H

R

J4

D14

J10

G2

12 3

G1

G2

AK I N

12 3

G1

G2

AK I N

12 3

G1

DIAGRAM 9:  CONNECTING STEAMERS

PRIMARY STEAMER

SECONDARY STEAMER

SECONDARY STEAMER

Summary of Contents for WWSU08

Page 1: ...teamer should be the primary unit Each steamer should have its own automatic drain For commercial use we recommend checking with your local inspectors to confirm the steamer system is acceptable for y...

Page 2: ...age Important Safety Instruction 3 6 1 Mounting the Generator 7 8 2 Water Quality Requirements 8 3 Plumbing Instructions 9 12 4 Wiring Instructions 12 Electrical Information Chart 13 5 Bath Control In...

Page 3: ...ng must be installed by a licensed plumber in accordance with all applicable local and national codes Install indoors only Protect from freezing Generator must be level side to side and end to end The...

Page 4: ...erie doit tre install par un plombier sous licence conform ment tous les codes locaux et nationaux applicables Installer l int rieur uniquement Prot ger du gel G n rateur doit tre mise niveau lat rale...

Page 5: ...ERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 5 of 17 POST WARNING LABEL OUTSIDE STEAMBATH FOR SAFETY WARNINGS tiquette d avertissement Ext rieur poste baiin de vapeur pour les avertissements re...

Page 6: ...utilis par toute personne y compris les enfants avec toutes leurs capacit s physiques sensorielles ou mentales ou qui manquent d exp rience ou de connaissances moins qu ils aient la supervision ou de...

Page 7: ...ervice Provide clearance for plumbing and electrical service and for element removal See Diagram 1 6 The steam line should slope to allow condensation to drain The mounting location should minimize th...

Page 8: ...ale to form on the internal surfaces This deposit or scale can interfere with the equipment s proper operation and even cause premature boiler or generator failure Concentration of impurities is gener...

Page 9: ...ator to allow for future servicing if needed and for emergency shut off Make sure the shut off is open providing water to the generator before turning it on IMPORTANT Water pressure required 20 100 ps...

Page 10: ...5 mm hole for the steam line entry Center the 1 2 copper steam pipe in the hole See Diagram 4 Terminate the steam line with a 1 2 NPT male adapter Stub the line out into the room 3 8 9 5 mm from the f...

Page 11: ...t have a drain valve installed to allow draining the tank for cleaning and maintenance A manual ball valve is supplied An electronic ball valve is available in the ADK Autodrain option When installed...

Page 12: ...dicated on the wire diagram for your voltage and phase This may require moving factory installed jumper Do not change the steamer s internal jumpers or wiring Only the supply wiring side of the termin...

Page 13: ...240 208 230 240 WWSU08 208 36 50 240 30 31 40 40 WWSU11 208 18 36 30 50 240 44 46 60 60 WWSU15 208 24 42 30 60 240 20 36 21 38 30 50 30 50 Nominal Amps at operating VAC 3 phz Recommended Breaker Mode...

Page 14: ...room The K3 and KT3 controls have a short tube on the back to help locate the control and to protect the cable end All of these controls connect to the steam generator s circuit board through Waterwor...

Page 15: ...or leaks 2 After the tank has filled to a safe level the heating elements will turn on Allow about 10 minutes for the steam to appear in the steam room 3 Once the steam is visible use the control to t...

Page 16: ...INSTALLATION AND SERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 16 of 17...

Page 17: ...INSTALLATION AND SERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 17 of 17 240V MODELS 208V MODELS...

Page 18: ...drain For commercial use we recommend checking with your local inspectors to confirm the steamer system is acceptable for your use Many jurisdictions will require an ASME boiler for commercial use WA...

Page 19: ...ION continued IMPORTANT Before deciding on a mounting location please read through these installation instructions completely and take a careful look at al of the diagrams An exhaust fan installed out...

Page 20: ...YPICAL DRAIN LINES DIAGRAM 5 TYPICAL STEAM LINES IMPORTANT Input water pressure must be 20 100 psi 138 689 kPa If the generators are mounted in a place difficult for the home owner to access the water...

Page 21: ...instructions document 4211 1661 for details regarding plumbing of the individual steamers in your system INSTALL THE PRESSURE RELIEF VALVE Each steamer must have its own pressure safety valve 10psi 69...

Page 22: ...Refer to the wiring diagrams to determine your connection points and the necessary jumper connection Connections can be varied to use either single phase or 3 phase or 3 phase Neutral Connect the eart...

Page 23: ...s the ON OFF switch 6 Within one minute the units should again produce steam The generators should call for water once every two minutes or more depending on their power rating It s normal for the flo...

Page 24: ...TERIORCONTROLISMOUNTEDOUTSIDETHEENCLOSURETO ALLOW FOR EASY ADJUSTMENTS TO THE TIME AND TEMPERATURE STEAMBATH SCHEDULE THE INTERIOR CONTROLIS MOUNTED INSIDE THE ENCLOSURE TO ALLOW TEMPERATURE SENSING A...

Page 25: ...Description Page Important Safety Instructions 3 1A Exterior Control Overview 4 1B Interior Control Overview 4 2 Operation of Your WWSUP18 and WWSUP19 Controls 4 3 How toTake a Steambath 4 4 Maintena...

Page 26: ...hould consult a physician regarding correct exposure e Obese persons and persons with a history of heart disease low or high blood pressure circulatory system problems or diabetes should consult a phy...

Page 27: ...The control will alternately display time remaining and the actual temperature at the sensor in your steam room every 5 seconds 4 To change the time setting press and hold the TIME button on the cont...

Page 28: ...emperature adjustment needs setting 1 See Section 3 Temperature Adjustment 2 Call WATERWORKS Service Department Control ON exterior or interior Control displays E001 Temperature sensor not connected 1...

Page 29: ...4209 55 REV A 01 28 2022 WWSU46 OWNERS MANUAL page 6...

Reviews: