C
ONVERTED
115 V
OLT
30 A
MP
C
ONFIGURATION
C
ONVERSION INSTRUCTIONS
NOTE:
An Authorized Solana
™
Spa Technician must perform the conversion.
1. Disconnect power to the spa and access the control box.
2. Locate the program jumpers (JM1, JM2 and JM3) at the bottom right of the control box (see Figure 1).
3. Using a pair of needle nose pliers, carefully move the JM1 jumper from pins 2 and 3 to pins 1 and 2 (see Figure 2).
A licensed electrician must install the sub-panel (available from your Solana
™
Spa Dealer) to supply
power to the spa. The sub-panel must be placed in sight of the spa, at a minimum distance of 5 feet away.
16
™
Figure 1
Figure 2:
Converted 115 Volt
30 amp jumper configuration
(See Figure 2
for jumper
configuration.)
Summary of Contents for Solana
Page 1: ...Watkins Manufacturing Corporation OWNER S MANUAL...
Page 2: ......
Page 61: ...NOTES 59...
Page 62: ...NOTES 60...