Chapter 5: LogicPro and Modbus Reference
PPC-2000 User’s Guide
194
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
Alarm Delay
This value delays alarm reporting, to prevent the reporting of
false alarms due to noise on the input. The alarm delay applies
to failed sensor alarms and process and deviation alarms. Only
alarms that are present for longer than the alarm delay time
are reported. The alarm delay is set in seconds.
NOTE!
Use the Database Offset number of an output for the
alarm output value. See Table 5.33 on page 196
through Table 5.36 on page 199.
If more than one alarm is assigned to the same output
number, that output will be on if any of those alarms
is active.
High Process Output Destination (HP Output Dest)
Choose the digital output that is toggled when the high process
alarm occurs. This can be any available hardware output or a
Boolean register accessible to the logic program. The default
high process alarm output is 0. When 0 is selected there is no
output.
Low Process Output Destination (LP Output Dest)
Choose the digital output that is toggled when the low process
alarm occurs. This may be any available hardware output a
Boolean register accessible to the logic program. The default
alarm output is 0. When 0 is selected there is no output.
High Deviation Output Destination (HD Output Dest)
Choose the digital output that is toggled when the high
deviation alarm occurs. This may be any available hardware
output or a Boolean register accessible to the logic program.
The default alarm output is 0. When 0 is selected there is no
output.
Low Deviation Output Destination (LD Output Dest)
Choose the digital output that is toggled when the low
deviation alarm occurs. This may be any available hardware
output or a Boolean register accessible to the logic program.
The default alarm output is 0. When 0 is selected there is no
output.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...