PPC-2000 User’s Guide
Chapter 5: LogicPro and Modbus Reference
Doc.# 30002-00 Rev 2.3
Watlow Anafaze
207
Accessing Global Parameters with
LogicPro
When a logic program variable accesses global parameters, the
parameter number (#) and the offset are used in conjunction
with the
LogicPro
Database I/O driver. The I/O physical
address is constructed from the parameter number and the
database offset.
See the
LogicPro User’s Guide
for specific instructions on
addressing global parameters. See
and
for the parameter number (#) and the
parameter descriptions for database offsets for each global
parameter.
Communications Parameters
For multiple PPC installations, each PPC must have a unique
network address. As many as 32 PPC systems may
communicate on a network. Network addresses 1 through 4 can
be set using the rotary switch on the processor module.
Use setting
D
and
PPCComSU
to program the remaining
addresses (5-32). Refer to
Changed communication parameters do not take affect until
the controller resets or cycles power, and only with the
appropriate rotary switch settings on the Processor module.
NOTE!
Do not cycle power with the rotary switch set in
positions E-G unless specifically directed to do so.
These positions are used for clearing memory and
other functions. Parameter settings can be lost. See
Chapter 4, Troubleshooting, for more on these switch
settings.
Table 5.47
Rotary Switch Configuration
Position
Network Address
A
Fixed: 1
B
Fixed: 2
C
Fixed: 3
D
Programmable, Default: 4
E-G
N/A
H
Fixed: 1
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...