Chapter 4: Troubleshooting
PPC-2000 User’s Guide
156
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
ç
CAUTION!
Do not perform this procedure at a time during which
closed-loop control and logic program outputs
should not be turned off.
1.
Remove power from the PPC-2000 system.
2.
Set the rotary switch on the Processor module to position
H
.
3.
Power up the PPC-2000 system.
4.
Set the communications parameters used by the host
device or software to the appropriate values for setting
H
:
Network address:
1
Baud rate:
19.2
kbaud
Parity:
Even
Data bits:
8
Stop bits:
1
5.
Attempt to communicate.
If the PPC-2000 still will not communicate and all other com-
ponents and settings have been verified, contact technical
support at the number in the front of this manual.
Resetting Closed-Loop Control Parameters
To restore all the closed-loop control, alarm, global and I/O
parameters to their factory default settings, perform the fol-
lowing procedure:
NOTE!
This procedure erases ALL user settings including
I/O assignments and restores all parameters to the
factory defaults, and all retained logic program values
are reset. Make a record of all settings you may wish
to restore before performing this procedure. A
Snapshot may be made in AnaWin3 to record closed-
loop control parameters for future downloading.
This procedure resets the programmable
communications parameters and restores them to the
factory defaults. Make a record of all settings you may
wish to restore before performing this procedure.
After performing the following procedure, refer to
Programmable Modbus Addresses on page 87
, if necessary, to
reprogram the Modbus address or baud rate.
Summary of Contents for Anafaze PPC-2000
Page 2: ......
Page 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Page 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Page 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Page 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...