Watlow D4T Data Logger
•
105
•
Chapter 5 Function Reference
Function
To sum up to four inputs, set Function to
Add
.
Offset
Adjustment added to the result of the calculation.
Range: -99,999.000 to 99,999.000
Filter
Set the amount of filtering to apply. Filtering smooths signal fluctuations. Increase the time to
increase filtering. Excessive filtering slows the function’s response.
Range: 0.0 to 60.0 seconds
Multiply
This function multiplies up to four inputs. Only inputs connected to a source are used in the
calculation. A filter and offset may be applied to the calculated value. If any input is an ab-
solute temperature, the output is also an absolute temperature; otherwise the output’s units
are those of the signal connected to the top input.
Signals
Direction
Label
Type
Function
Receivers
- - - - Analog
Value to be multiplied
- - - - Analog
Value to be multiplied
- - - - Analog
Value to be multiplied
- - - - Analog
Value to be multiplied
Transmitter - - - - Analog
The filtered product of the inputs plus the offset
Function
To compute the product of up to four inputs, set Function to
Multiply
.
Offset
Adjustment added to the result of the calculation.
Range: -99,999.000 to 99,999.000
Filter
Set the amount of filtering to apply. Filtering smooths signal fluctuations. Increase the time to
increase filtering. Excessive filtering slows the function’s response.
Range: 0.0 to 60.0 seconds
Absolute Difference
This function calculates the absolute value of input X minus input Y. A filter and offset may
be applied to the calculated value. The output has the units of input x.