Watlow D4T Data Logger
•
170
•
Chapter 6 Appendix
Parameter Class
and Name
Range
Default
Data Type and
Attributes
Modbus Registers
Sensor Type
"Off (62)
Thermocouple (95)
Millivolts (56)
Volts (104)
Milliamps (112)
RTD 100 Ohm (113)
RTD 1000 Ohm (114)
1K Potentiometer (155)"
Thermocouple (95)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27594
Universal Input 1:
Module 2, 28034
Universal Input 1:
Module 3, 28474
Universal Input 1:
Module 4, 28914
Universal Input 1:
Module 5, 29354
Universal Input 1:
Module 6, 29794
Add 110 for the
address of the next
input"
TC Linearization
"B (11)
C (15)
D (23)
E (26)
F (30)
J (46)
K (48)
N (58)
R (80)
S (84)
T (93)"
J (46)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27596
Universal Input 1:
Module 2, 28036
Universal Input 1:
Module 3, 28476
Universal Input 1:
Module 4, 28916
Universal Input 1:
Module 5, 29356
Universal Input 1:
Module 6, 29796
Add 110 for the
address of the next
input"
RTD Leads
"2 (1)
3 (2)"
2 (1)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27598
Universal Input 1:
Module 2, 28038
Universal Input 1:
Module 3, 28478
Universal Input 1:
Module 4, 28918
Universal Input 1:
Module 5, 29358
Universal Input 1:
Module 6, 29798
Add 110 for the
address of the next
input"
Scale Low
-100 To 1000
0.0
"IEEE Float
Access=RW"
"Universal Input 1:
Module 1, 27600
Universal Input 1:
Module 2, 28040
Universal Input 1:
Module 3, 28480
Universal Input 1:
Module 4, 28920
Universal Input 1:
Module 5, 29360
Universal Input 1:
Module 6, 29800
Add 110 for the
address of the next
input"