Watlow D4T Data Logger
•
172
•
Chapter 6 Appendix
Parameter Class
and Name
Range
Default
Data Type and
Attributes
Modbus Registers
Process Error Low
Value
-100 To 1000
0.0
"IEEE Float
Access=RW"
"Universal Input 1:
Module 1, 27610
Universal Input 1:
Module 2, 28050
Universal Input 1:
Module 3, 28490
Universal Input 1:
Module 4, 28930
Universal Input 1:
Module 5, 29370
Universal Input 1:
Module 6, 29810
Add 110 for the
address of the next
input"
Display Precision
"Whole (105)
Tenths (94)
Hundredths (40)
Thousandths (96)"
Whole (105)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27612
Universal Input 1:
Module 2, 28052
Universal Input 1:
Module 3, 28492
Universal Input 1:
Module 4, 28932
Universal Input 1:
Module 5, 29372
Universal Input 1:
Module 6, 29812
Add 110 for the
address of the next
input"
Units
"Absolute Temperature
(1540)
Power (73)
Process (75)
Relative Humidity
(1538)"
Process (75)
"unsigned 16-bit
Access = RW"
"Universal Input 1:
Module 1, 27614
Universal Input 1:
Module 2, 28054
Universal Input 1:
Module 3, 28494
Universal Input 1:
Module 4, 28934
Universal Input 1:
Module 5, 29374
Universal Input 1:
Module 6, 29814
Add 110 for the
address of the next
input"
Calibration Offset
-99999 To 99999
0.0
"IEEE Float
Access=RW"
"Universal Input 1:
Module 1, 27616
Universal Input 1:
Module 2, 28056
Universal Input 1:
Module 3, 28496
Universal Input 1:
Module 4, 28936
Universal Input 1:
Module 5, 29376
Universal Input 1:
Module 6, 29816
Add 110 for the
address of the next
input"