Watlow D4T Data Logger
•
178
•
Chapter 6 Appendix
Parameter Class
and Name
Range
Default
Data Type and
Attributes
Modbus Registers
Coefficient A
-3.4E+38 To 3.4E+38
1.471388e-3
"IEEE Float
Access=RW"
"Thermistor Input 1:
Module 1, 30240
Thermistor Input 1:
Module 2, 30560
Thermistor Input 1:
Module 3, 30880
Thermistor Input 1:
Module 4, 31200
Thermistor Input 1:
Module 5, 31520
Thermistor Input 1:
Module 6, 31840
Add 80 for the
address of the next
input"
Coefficient B
-3.4E+38 To 3.4E+38
2.376138e-4
"IEEE Float
Access=RW"
"Thermistor Input 1:
Module 1, 30242
Thermistor Input 1:
Module 2, 30562
Thermistor Input 1:
Module 3, 30882
Thermistor Input 1:
Module 4, 31202
Thermistor Input 1:
Module 5, 31522
Thermistor Input 1:
Module 6, 31842
Add 80 for the
address of the next
input"
Coefficient C
-3.4E+38 To 3.4E+38
1.051058e-7
"IEEE Float
Access=RW"
"Thermistor Input 1:
Module 1, 30244
Thermistor Input 1:
Module 2, 30564
Thermistor Input 1:
Module 3, 30884
Thermistor Input 1:
Module 4, 31204
Thermistor Input 1:
Module 5, 31524
Thermistor Input 1:
Module 6, 31844
Add 80 for the
address of the next
input"
Display Precision
"Whole (105)
Tenths (94)
Hundredths (40)
Thousandths (96)"
Whole (105)
"unsigned 16-bit
Access = RW"
"Thermistor Input 1:
Module 1, 30252
Thermistor Input 1:
Module 2, 30572
Thermistor Input 1:
Module 3, 30892
Thermistor Input 1:
Module 4, 31212
Thermistor Input 1:
Module 5, 31532
Thermistor Input 1:
Module 6, 31852
Add 80 for the
address of the next
input"