182
•
Chapter 6 Appendix
Parameter Class
and Name
Range
Default
Data Type and
Attributes
Modbus Registers
)
Output Type
"Volts (104)
Milliamps (112)"
Volts (104)
"unsigned 16-bit
Access = RW"
"Analog Output 1:
Module 1, 32566
Analog Output 1:
Module 2, 32716
Analog Output 1:
Module 3, 32866
Analog Output 1:
Module 4, 33016
Analog Output 1:
Module 5, 33166
Analog Output 1:
Module 6, 33316
Add 50 for the
address of the next
Analog Ouput"
Function
"Off (62)
Analog Input (142)
Current (22)
Cool Power (161)
Heat Power (160)
Power (73)
Linearization (238)
Math (240)
Process Value (241)
Set Point Closed (242)
Set Point Open (243)
Special Function Output
1 (1532)
Special Function Output
2 (1533)
Special Function Output
3 (1534)
Special Function Output
4 (1535)
Variable (245)
Condition (10001)
Encoder (1740)
Off (62)
"unsigned 16-bit
Access = RW"
"Analog Output 1:
Module 1, 32568
Analog Output 1:
Module 2, 32718
Analog Output 1:
Module 3, 32868
Analog Output 1:
Module 4, 33018
Analog Output 1:
Module 5, 33168
Analog Output 1:
Module 6, 33318
Add 50 for the
address of the next
Analog Ouput"
Output Function
Instance
1 To 250
1
"unsigned 8-bit
Access=RW"
"Analog Output 1:
Module 1, 32572
Analog Output 1:
Module 2, 32722
Analog Output 1:
Module 3, 32872
Analog Output 1:
Module 4, 33022
Analog Output 1:
Module 5, 33172
Analog Output 1:
Module 6, 33322
Add 50 for the
address of the next
Analog Ouput"