Watlow D4T Data Logger
•
87
•
Chapter 5 Function Reference
Input Point 3
Set the third lowest input value to be scaled. Input values equal to or greater than this, but
less than Input Point 4 are scaled to Output Point 3.
Range: -99,999.000 to 99,999.000
Output Point 3
Set the value to which the input is scaled when the input is greater than or equal to Input
Point 3 and less than Input Point 4.
Range: -99,999.000 to 99,999.000
Input Point 4
Set the forth lowest input value to be scaled. Input values equal to or greater than this, but
less than Input Point 5 are scaled to Output Point 4.
Range: -99,999.000 to 99,999.000
Output Point 4
Set the value to which the input is scaled when the input is greater than or equal to Input
Point 4 and less than Input Point 5.
Range: -99,999.000 to 99,999.000
Input Point 5
Set the fifth lowest input value to be scaled. Input values equal to or greater than this, but
less than Input Point 6 are scaled to Output Point 5.
Range: -99,999.000 to 99,999.000
Output Point 5
Set the value to which the input is scaled when the input is greater than or equal to Input
Point 5 and less than Input Point 6.
Range: -99,999.000 to 99,999.000
Input Point 6
Set the sixth lowest input value to be scaled. Input values equal to or greater than this, but
less than Input Point 7 are scaled to Output Point 6.
Range: -99,999.000 to 99,999.000
Output Point 6
Set the value to which the input is scaled when the input is greater than or equal to Input
Point 6 and less than Input Point 7.
Range: -99,999.000 to 99,999.000
Input Point 7
Set the seventh lowest input value to be scaled. Input values equal to or greater than this,
but less than Input Point 8 are scaled to Output Point 7.
Range: -99,999.000 to 99,999.000